HEATING LOAD FORM
FRIEDRICH ROOM UNIT HEAT PUMPS
 
 
BTU/HR PER
WALLS: (Linear Feet) 
°F TEMP. DIFFERENCE
 
2” Insulation 
Lin. Ft. x 1.6
 
Average 
Lin. Ft. x 2.6
WINDOWS & DOORS (Area, sq. ft.) 
 
Single Glass: 
Sq. Ft. x 1.13
 
Double Glass: 
Sq. Ft. x  0.61
INFILTRATION - WINDOWS & DOORS: AVG. 
Lin. Ft. x 1.0
 
                            Loose 
Lin. Ft. x 2.0
CEILING: (Area, Sq. Ft.) 
 
Insulated (6”) 
Sq. Ft. x 0.07
 
Insulated (2”) 
Sq. Ft. x 0.10
 
Built-up Roof (2” insulated 
Sq. Ft. x 0.10
 
Built-up Roof (1/2” insulated) 
Sq. Ft. x 0.20
 
No Insulation 
Sq. Ft. x 0.33
FLOOR: (Area, Sq. Ft.)
 
Above Vented Crawl space
 
Insulated (1:) 
Sq. Ft. x 0.20
 
Uninsulated 
Sq. Ft. x 0.50
 
* Slab on Ground 
Lin. Ft. x 1.70
 
1” Perimeter insulation 
Lin. Ft. x 1.00
*  Based on Linear Feet of outside wall 
TOTAL HEAT LOSS PER °F  BTU/HR/°F
Multiply total BTU/HR/°F X 30 and plot on the graph below at 40°F.  Draw a straight line from 
the 70 base point thru the point plotted at 40°F.  The intersection of this heat loss line with the 
unit capacity line represents the winter design heating load.