Installation Instructions 
Lateral Duct Accessory Kit 
For Use with F Series Packaged Terminal Air Conditioner or Heat Pump  
Introduction: 
These instructions cover the installation of the Lateral Duct Accessory Kit for Packaged Terminal Air 
Conditioner (PTAC) units.  Please read these instructions completely before attempting installation. 
 
Package Contents (
See Fig 1):
 
ITEM QUANTITY 
Plenum 1 
Extension Duct 
Extension Duct Wall Trim Kit 
Wall Register 
End Cap 
Attachment Screws 
14 
Right Support Bracket 
Left Support Bracket 
 
Tools Required:  Power drill, 1/8” drill bit, hacksaw, Phillips screwdriver and utility knife. 
 
 
General 
The Lateral Duct Accessory Kit allows one PTAC unit to heat or cool two rooms.  The kit mounts to 
the wall sleeve and can be installed for either right or left side duct applications.  The amount of air 
that can be diverted to an adjoining room is adjustable from 20 to 30 percent.  (See Table 1) 
 
Table 1 – Airflow Adjustments 
BAFFLE POSITION 
UNIT FRONT 
ADJACENT ROOM 
Position 1 (factory default) 
80% 
20% 
Position 2 
75% 
25% 
Position 3 
70% 
30% 
  
Pre-Installation 
Consider the following before installing the Lateral Duct Accessory: 
• 
Maximum duct extension length is 4 feet. 
• 
Duct run must be straight and horizontal; no bends or turns. 
• 
Minimum recommended clearance between unit and adjoining room wall is 6 inches. 
• 
Provisions must be made for return air from the adjoining room. 
• 
The PTAC unit does not have to be removed for lateral duct installation. 
 
 
 
 
Figure 1- Components for Lateral Duct Accessory Kit