Friedrich H)A12K34L Manuale Utente

Pagina di 45
Overcharged Refrigerant systems
After the unit has run 10 to 15 minutes, check the gauge 
pressures. Gauges connected to system with an undercharge 
will  have low head pressures and substantially low suction  
pressures.  
Improper  air  flow  over  the  evaporator  coil  may  indicate 
some of the same symptoms as an over charged system. 
An  overcharge  can  cause  the  compressor  to  fail,  since  it  
would be “slugged” with liquid refrigerant. 
The charge for any system is critical. When the compressor 
is noisy, suspect an overcharge, when you are sure that the 
air quantity over the evaporator coil is correct. Icing of the 
evaporator will not be encountered because the refrigerant 
will boil later if at all. Gauges connected to system will usually 
have higher head pressure (depending upon amount of over 
charge). Suction pressure should be slightly higher. 
Compressor  amps  will  be  near  normal  or  higher. 
Noncondensables  can  also  cause  these  symptoms.  To 
confirm, remove some of the charge, if conditions improve, 
system may be overcharged. If conditions don’t improve, 
Noncondensables are indicated. 
Whenever an overcharged system is indicated, always make 
sure that the problem is not caused by air flow problems.     
Restricted Refrigerant system 
Troubleshooting  a  restricted  refrigerant  system  can  be 
difficult. The following procedures are the more common 
problems and solutions to these problems. There are two 
types  of  refrigerant  restrictions:  Partial  restrictions  and 
complete restrictions. 
A  partial  restriction  allows  some  of  the  refrigerant  to 
circulate through the system. 
With  a  complete  restriction  there  is  no  circulation  of 
refrigerant in the system. 
Restricted refrigerant systems display the same symptoms 
as a “low-charge condition.” 
When the unit is shut off, the gauges may equalize very  
slowly. 
Gauges connected to a completely restricted system will 
run in a deep vacuum. When the unit is shut off, the gauges 
will not equalize at all.
A quick check for either condition begins at the evaporator. 
With  a  partial  restriction,  there  may  be  gurgling  sounds 
at  the  metering  device  entrance  to  the  evaporator.  The 
evaporator in a partial restriction could be partially frosted 
or have an ice ball close to the entrance of the metering 
device. Frost may continue on the suction line back to the 
compressor. 
Often a partial restriction of any type can be found by feel, 
as there is a temperature difference from one side of the 
restriction to the other. 
With a complete restriction, there will be no sound at the 
metering  device  entrance.  An  amperage  check  of  the 
compressor  with  a  partial  restriction  may  show  normal 
current when compared to the unit specification. 
With  a  complete  restriction  the  current  drawn  may  be 
considerably  less  than  normal,  as  the  compressor  is 
running in a deep vacuum (no load.) Much of the area of 
the condenser will be relatively cool since most or all of the 
liquid refrigerant will be stored there. 
The following conditions are based primarily on a system 
in the cooling mode.
23