Fedders AZFPC60B1 Manuale Utente

Pagina di 6
Product Specifications
3
Specifications subject to change without notice.
Specifications applicable to upflow and horizontal applications.
Air flow shown at the following conditions:
- No heat elements in Air Handler. Decrease CFM 2% for 5 kW, 7.5 kW or 10 kW heat kits. Decrease CFM 1% for 15 kW or 20 kW heat kits.
- 60 Hertz – 230 volts. Decrease CFM 6% for 208 volt operations.
- Dry coil airflow shown.
AIRFLOW PERFORMANCE
MODEL
NUMBER
BLOWER
SPEED
MEASURED STATIC PRESSURE INLET TO OUTLET 
(INCHES WATER COLUMN)
0.20
0.30
0.40
0.50
0.60
AFPB24A1
HIGH
925
900
850
795
690
MEDIUM
800
760
745
670
N/A
LOW
655
625
600
N/A
N/A
AFPB24B1
HIGH
905
880
830
780
680
MEDIUM
785
735
730
655
N/A
LOW
645
615
590
N/A
N/A
AFPB36A1
HIGH
1440
1350
1260
1180
1040
MEDIUM
1300
1220
1050
940
860
LOW
1160
1070
950
880
780
AFPC48A1
AFPC48B1
HIGH
1680
1640
1590
1520
1430
MEDIUM
1440
1410
1380
1340
1250
LOW
1240
1220
1190
1150
1100
AFPC60A1
AZFPC60B1
HIGH
2230
2105
1990
1895
1725
MEDIUM
1950
1930
1840
1770
1590
LOW
1360
1360
1350
1340
1080