Goodman Mfg GSX130181E Manuale Utente

Pagina di 44
P
roduct
 S
PecificationS
SS-GSX13
www.goodmanmfg.com
3
S
peCifiCAtionS
GSX13
0181E*
GSX13
0241D*
GSX13
0301B*
GSX13
0361C*
GSX13 
0361E*
GSX13
0421B*
GSX13
0481B*
GSX13
0601B*
GSX13
0611A*
Capacities
Nominal Cooling (BTU/h)
18,000
24,000
30,000
36,000
36,000
42,000
48,000
60,000
60,000
SEER / EER
13 / 11
13 / 11
13 / 11
13 / 11
13 / 11
13 / 11
13 / 11
13 / 11
13/11
Decibels
75
75
73
74
74
75
76
77
72
Compressor
RLA
6.7
13.5
12.8
14.1
14.1
17.9
19.9
25.0
26.4
LRA
41
58.3
64
77
77
112
109
134
134
Condenser Fan Motor
Horsepower
1/8
1/8
1/8
1/6
1/4
1/4
1/4
1/4
1/4
FLA
0.7
0.7
0.7
1.1
1.5
1.5
1.5
1.5
1.5
Refrigeration System
Refrigerant Line Size ¹
Liquid Line Size (“O.D.)
⅜"
⅜"
⅜"
⅜"
⅜"
⅜"
⅜"
⅜"
⅜"
Suction Line Size (“O.D.)
¾"
¾"
¾"
⅞"
⅞"
1⅛"
1⅛"
1⅛"
⅞"
Refrigerant Connection Size
Liquid Valve Size (“O.D.)
⅜"
⅜"
⅜"
⅜"
⅜"
⅜"
⅜"
⅜"
⅜"
Suction Valve Size (“O.D.) ⁴ ⁵
¾"
¾"
¾"
¾" ⁴
¾" ⁴
⅞" ⁵
⅞" ⁵
⅞" ⁵
¾"
Valve Type
Sweat
Sweat
Sweat
Sweat
Sweat
Sweat
Sweat
Sweat
Sweat
Refrigerant Charge
73
76
78
89
75
90
104
111
130
Shipped with Orifice Size
0.051
0.057
0.061
0.070
0.070
0.076
0.080
0.086
0.086
Electrical Data
Voltage
208/230
208/230
208/230
208/230
208/230
208/230
208/230
208/230
208/230
Minimum Circuit Ampacity ²
9.1
17.6
16.7
18.7
19.1
23.9
26.4
32.8
34.5
Max. Overcurrent Protection ³
15 amps
30 amps
25 amps
30 amps
30 amps
40 amps
45 amps
50 amps
60 amps
Min / Max Volts
197/253
197/253
197/253
197/253
197/253
197/253
197/253
197/253
197/253
Electrical Conduit Size
½" or ¾"
½" or ¾"
½" or ¾"
½" or ¾"
½" or ¾"
½" or ¾"
½" or ¾"
½" or ¾"
½" or ¾"
Equipment Weight (lbs)
106
113
142
139
139
188
191
207
284
Ship Weight (lbs)
120
130
159
157
157
206
209
225
301
¹    Line sizes denoted for 25’ line sets, tested and rated in accordance with AHRI Standard 210/240. For other line-set lengths or sizes, refer  
to the installation & Operating instructions and/or the long line-set guidelines.
²    Wire size should be determined in accordance with National Electrical Codes; extensive wire runs will require larger wire sizes
³    Must use time-delay fuses or HACR-type circuit breakers of the same size as noted.
⁴    Installer will need to supply ¾” to ⅞” adapters for suction line connections.
⁵    Installer will need to supply ⅞” to 1⅛” adapters for suction line connections.
Notes
•  Always check the S&R plate for electrical data on the unit being installed.
•  Unit is charged with refrigerant for 15’ of ⅜” liquid line. System charge must be adjusted per Installation Instructions Final Charge Procedure.