York YPAL 060 Manuale Utente

Pagina di 168
152
JOHNSON CONTROLS
FORM 100.50-NOM6 (1207)
Parameter Description and Options
MENU ITEM
DEFINITION
SUPPLY AIR TEMP LIMIT FOR COOLING 
ENABLE
THIS PARAMETER MUST BE TURNED ON TO ENABLE SUPPLY 
AIR TEMP LIMIT OPERATION IN THE COOLING MODE ON A 
CONSTANT VOLUME UNIT
SUPPLY AIR TEMP LIMIT FOR HEATING 
ENABLED
THIS PARAMETER MUST BE TURNED ON TO ENABLE SUPPLY 
AIR TEMP LIMIT OPERATION IN THE HEATING MODE ON A 
CONSTANT VOLUME UNIT
SUPPLY AIR TEMP LIMIT HEATING SETPOINT
THIS PARAMETER IS USED BY THE UNIT CONTROLLER DURING 
SUPPLY AIR TEMP LIMIT FOR HEATING OPERATION ON A 
CONSTANT VOLUME UNIT.
TEMPERATURE/HUMIDITY (RETURN) CONTROL 
ENABLED
THIS PARAMETER WOULD BE USED IF HOT GAS REHEAT WAS 
BEING USED.  THIS FEATURE IS NOT AVAILABLE ON THESE 
UNITS.  THIS SHOULD ALWAYS BE SET TO OFF
THIRD PARTY BAS ECONOMIZER ENABLED
WHEN THIS PARAMETER IS TURNED ON THE POSITION OF THE 
ECONOMIZER DAMPER IS CONTROLLED BY AN EXTERNAL 2-10 
VDC INPUT
TURN OFF CONTINUOUS FAN WHEN STARTING 
HEAT
IF THIS PARAMETER IS TURNED ON AND THE UNIT IS RUNNING 
CONTINUOUS FAN, THE CONTROL WILL STOP THE SUPPLY FAN 
AT THE START OF A HEATING CYCLE AND TURN IT BACK ON 
BASED ON THE FAN ON FOR HEAT SETTING
UNIT MODEL NUMBER
THIS ALLOWS THE UNIT MODEL NUMBER TO BE ENTERED FOR 
THE UNIT THROUGH THE SIMPLICITY PC SOFTWARE
UNIT NAME
THIS ALLOWS A NAME TO BE ASSIGNED TO THE UNIT TO 
IDENTIFY IT ON THE NETWORK THROUGH THE SIMPLICITY PC 
SOFTWARE
UNIT SERIAL NUMBER
THIS ALLOWS THE UNIT SERIAL NUMBER TO BE ENTERED FOR 
THE UNIT THROUGH THE SIMPLICITY PC SOFTWARE
UNOCCUPIED OVERRIDE TIME PERIOD
THIS PARAMETER ESTABLISHES THE MAXIMUM TIME THE UNIT 
WILL REMAIN IN THE UNOCCUPIED OVERRIDE MODE WHEN 
THE OVERRIDE BUTTON IS PUSHED ON THE SPACE SENSOR.
VAV / CV SELECTION
THIS PARAMETER GIVES THE STATUS OF THE SET UP OF THE 
UNIT , VAV OR CV
VAV COOLING SUPPLY AIR TEMP LOWER 
SETPOINT
THIS PARAMETER ESTABLISHES THE LOWER COOLING 
SETPOINT FOR VAV COOLING OPERATION
VAV COOLING SUPPLY AIR TEMP UPPER 
SETPOINT
THIS PARAMETER ESTABLISHES THE UPPER COOLING 
SETPOINT FOR VAV COOLING OPERATION
VAV OCCUPIED HEATING ENABLED
THIS PARAMETER MUST BE TURNED ON TO ALLOW OCCUPIED 
HEATING OPERATION.
VAV OCCUPIED HEATING SETPOINT
THE UNIT CONTROLLER COMPARES THE SPACE TEMPERATURE 
TO THIS VALUE AS ONE OF THE CRITERIA TO USE TO 
DETERMINE WHEN TO INITIATE VAV OCCUPIED HEATING 
OPERATION
VAV SUPPLY AIR TEMP RESET SETPOINT
THE UNIT CONTROLLER COMPARES THE SPACE OR RETURN 
AIR TEMPERATURE TO THIS VALVE TO DETERMINE IF IT 
SHOULD CONTROL TO THE VAV COOLING SUPPLY AIR UPPER 
OR LOWER SETPOINT
YEAR
THIS PARAMETER IS USED TO ENTER THE CURRENT YEAR 0 TO 
99.  FOR EXAMPLE 7 WOULD BE 2007
TABLE 7-1 – DEFINITIONS (CONTINUED)