York D1EE036 Manuale Utente

Pagina di 32
036-21411-002-A-0204
18
Unitary Products Group
TABLE 17: ELECTRICAL DATA COOLING/ELECTRIC HEAT W/ DIRECT DRIVE DEE048
MODEL
DEE
POWER
SUPPLY
HEATER
ACCESSORY
MODEL
NUMBER
SUPPLY
AIR
BLOWER
MOTOR
FLA
ELECTRIC HEATERS
MINIMUM
CIRCUIT
AMPACITY
MAX 
FUSE
SIZE
1
AMPS
MAX.
SIZE
HACR
2
kW
STAGES
TOTAL
AMPS
048
208-1-60
2CE04500506
5.0
4.0
1
19.1
38.6
60
60
2CE04500706
5.6
1
27.1
39.9
60
60
2CE04501006
8.0
1
38.3
54.3
60
60
2CE04501506
11.9
2
57.4
77.8
80
80
2CE04502006
15.9
2
76.6
101.8
110
110
230-1-60
2CE04500506
5.0
5.3
1
22.1
38.6
60
60
2CE04500706
7.5
1
31.3
45.3
60
60
2CE04501006
10.6
1
44.2
61.5
70
70
2CE04501506
15.9
2
66.3
89.1
90
90
2CE04502006
21.2
2
88.3
116.7
125
125
208-3-60
2CE04500525
3
5.0
4.0
1
11.0
25.7
40
40
2CE04500725
3
5.6
1
15.6
25.7
40
40
2CE04501025
8.0
1
22.1
34.0
40
40
2CE04501525
11.9
2
33.1
47.5
50
50
2CE04502025
15.9
2
44.2
61.4
70
70
230-3-60
2CE04500525
3
5.0
5.3
1
12.7
25.7
40
40
2CE04500725
3
7.5
1
18.0
28.8
40
40
2CE04501025
10.6
1
25.5
38.0
40
40
2CE04501525
15.9
2
38.2
54.0
60
60
2CE04502025
21.2
2
51.0
70.0
70
70
460-3-60
2CE04500746
3
2.2
6.8
1
8.2
13.2
20
20
2CE04501046
3
10.1
1
12.1
17.9
20
20
2CE04501546
3
13.6
1
16.4
23.2
25
25
2CE04502046
3
19.5
2
23.5
32.1
35
35
575-3-60
2CE04501058
2.2
10.6
1
10.2
15.5
20
20
2CE04501558
15.9
1
15.3
21.9
25
25
2CE04502058
21.2
2
20.4
28.2
30
30
1.
Dual element, time delay type.
2.
Standard circuit breakers may be used in Canada and on applications over 60 amps where the heaters are separately fused.
3.
These electric heaters DO NOT include a fuse box. If a fuse box is required to meet a local code (e.g. Chicago), the following fuse 
block accessories are available for field installation (see Table 19).
TABLE 18: ELECTRIC HEAT CORRECTION 
FACTORS
NOMINAL VOLTAGE
VOLTAGE
kW CAP. MULTIPLIER
208
208
1.00
240
230
0.92
480
460
0.92
600
575
0.92
TABLE 19: FUSE BLOCK ACCESSORY
PART NUMBER
VOLTS
2FB04700425
208/240 Volts
2FB04700546
460 Volts