AIR FLOW
AIR FLOW DATA - 60 Hz MODELS - 208 VOLT
Models
Blower 
Motor Speed
CFM
@ External Static Pressure - IWC
1. Dry coil conditions only, tested without filters.
Air handler units are CSA listed to UL 1995/CSA C22.2 236-05 up to 0.30" w.c. external static pressure, including air filter, wet coil, and largest kW size heater, unless 
otherwise noted.
Operation not recommended in shaded areas.
0.10
0.20
0.30
0.40
0.50
0.60
0.70
208 Volt
AHE18B3XH21
High #5
1074
1029
999
954
911
865
812
Med High #4
895
846
802
759
701
630
526
Med #3
663
610
556
482
334
219
173
Med Low #2
630
466
346
196
170
67
23
Low #1
630
466
346
196
170
67
23
AHE24B3XH21
High #5
1147
1107
1076
1040
992
942
861
Med High #4
1009
974
941
903
859
811
762
Med #3
826
785
744
690
639
566
501
Med Low #2
654
590
556
479
419
307
251
Low #1
580
491
425
317
224
189
73
AHE30B3XH21
High #5
1147
1107
1076
1040
992
942
861
Med High #4
1009
974
941
903
859
811
762
Med #3
826
785
744
690
639
566
501
Med Low #2
654
590
556
479
419
307
251
Low #1
580
491
425
317
224
189
73
AHE36C3XH21
High #5
1473
1417
1361
1304
1241
1171
1109
Med High #4
1257
1204
1138
1076
1000
928
856
Med #3
1069
997
912
831
772
697
617
Med Low #2
994
800
705
621
554
488
432
Low #1
904
692
411
329
256
152
NA
AHE42D3XH21
High #5
1619
1577
1531
1484
1428
1372
1307
Med High #4
1434
1391
1346
1292
1235
1164
1054
Med #3
1243
1192
1135
1073
978
882
778
Med Low #2
1141
1027
952
842
724
572
559
Low #1
1025
851
465
418
253
208
123
AHE48D3XH21
High #5
1847
1812
1775
1725
1684
1645
1600
Med High #4
1675
1640
1597
1561
1522
1479
1421
Med #3
1436
1394
1349
1301
1246
1182
1095
Med Low #2
1250
1211
1157
1100
1013
924
854
Low #1
1151
1029
965
857
779
720
639
AHE60D3XH21
High #5
2083
2042
2002
1959
1921
1875
1829
Med High #4
1893
1856
1815
1776
1728
1688
1639
Med #3
1642
1609
1564
1512
1467
1416
1340
Med Low #2
1443
1401
1360
1307
1242
1160
1062
Low #1
1259
1198
1140
1067
972
900
797