York AHP18 Manuale Utente

Pagina di 12
255029-YTG-M-0610
Johnson Controls Unitary Products
5
All air handler units are UL Listed up to 0.50" w.c. external static pressure, including air filter, wet coil, and largest KW size heater, unless otherwise 
noted.
AIR FLOW DATA - 60 Hz MODELS
Models
Blower
Motor
Speed
230 Volt
CFM
@ External Static Pressure - IWC
0.10
0.20
0.30
0.40
0.50
0.60
0.70
0.80
0.90
1.00
AHP18B**H21
High
1054
989
923
862
791
665
581
202
N/A
N/A
Medium
782
762
716
670
613
536
315
121
N/A
N/A
Low
541
519
479
445
397
298
168
N/A
N/A
N/A
AHP24B**H21
High
1232
1167
1098
1025
940
826
731
622
486
345
Medium
966
915
868
799
724
641
540
452
347
224
Low
785
740
684
618
532
446
364
296
192
131
AHP30B**H21
High
1434
1359
1297
1220
1138
1050
916
782
640
519
Medium
1112
1076
1031
970
907
802
629
507
394
380
Low
885
854
821
751
686
625
547
459
350
N/A
AHP36C**H21
High
1760
1681
1607
1538
1456
1360
1322
1260
966
770
Medium
1320
1284
1255
1207
1146
1075
988
846
729
572
Low
1146
1119
1090
1038
992
972
841
725
617
496
AHP42C**H21
High
1883
1764
1657
1543
1435
1327
1210
902
714
527
Medium
1625
1510
1429
1339
1256
1172
1038
765
609
412
Low
1260
1225
1179
1110
1047
973
785
638
500
340
AHP48D**H21
High
2029
1944
1837
1743
1643
1537
1435
1320
1064
789
Medium
1805
1730
1649
1566
1479
1385
1286
1147
851
683
Low
1491
1441
1388
1328
1253
1174
1076
867
726
555
AHP60D**H21
High / #1
2256
2226
2198
2159
2095
1959
1914
1776
1519
1380
Medium High / #2
1990
1963
1935
1893
1857
1820
1783
1698
1486
1353
Medium / #3
1774
1748
1704
1670
1635
1593
1534
1480
1384
1325
Medium Low / #4
1557
1523
1483
1432
1389
1329
1265
1235
1198
1167
Low / #5
1340
1300
1253
1198
1126
1079
1037
1007
954
912
1. Includes return air filter and coil.
APPLICATION FACTORS - RATED CFM VS. ACTUAL CFM
% Of Rated Airflow
80%
90%
Rated CFM
110%
120%
Capacity Factor
0.96
0.98
1.00
1.02
1.03