American Power Conversion DX Manuale Utente
NetworkAIR FM DX 60 Hz Operation, Maintenance, and Troubleshooting
26
Action.
Set the System controller to respond to the change of status for an input in one of the following
ways:
Map
Description/Function
Status Only
Displays the event on the Active Alarms screen. Status-only
events are not logged.
events are not logged.
Minor Alarm
Activates the Warning LED and the alarm beeper. It also creates
an entry in the event log.
an entry in the event log.
Major Alarm
Activates the Alarm LED and the alarm beeper. It also creates an
entry in the event log.
entry in the event log.
Remote Run/Stop
Shuts down the Modules normally, waiting for delay timers.
Nonessential Lockout
Deactivates modes set as nonessential and continues operation.
Immediate Shutdown
Shuts down the Modules immediately. It does not wait for the
blower delay or compressor timers.
blower delay or compressor timers.