InRoom Precision AC Tech Data Manual
12
InRoom Standard Condensers - 60 Hz
* Condenser connections may not represent actual line sizing.
** Dimensions are overall. Electrical enclosure and fan guard are included. Actual fan guard height is 4 in.
Actual electrical enclosure depth is 6.5 in.
InRoom Remote Outdoor Condenser Data, 95°F ambient, 120°F condensation - R407C
InRoom Cabinet Size
1
2
3
4
5
Total Heat Rejection 
(THR) BTU/h
96.219
165.496
225.435
279.262
380.436
CFM
8,394
19,325
18,609
17,604
27,963
Fan Diameter - in
19.69
24.80
24.80
24.80
24.80
Voltage Options
208-230/3/60
ACCD76000
ACCD76004
ACCD76008
ACCD76012
ACCD76016
Number of Fans
2
2
2
2
3
Fan RPM (Qty)
1490
1585(1), 1500(1) 1585(1), 1500(1) 1585(1), 1500(1) 1585(2), 1500(1)
Motor HP (Qty)
1.23 Hp(2)
3.58(1), 3.85(1) 3.58(1), 3.85(1)
3.58(1), 3.85(1)
3.58(2), 3.85(1)
Electrical Data
FLA
8.6
19.7
19.7
19.7
29.1
MCA
9.8
22.1
22.1
22.1
31.5
MFS
15
30
30
30
40
460-480/3/60 ACCD76010
ACCD76005
ACCD76009
ACCD76013
ACCD76017
Number of Fans
2
2
2
2
3
Fan RPM (Qty)
1450(1), 1570(1)1650(1), 1500(1) 1650(1), 1500(1) 1650(1), 1500(1) 1650(2), 1500(1)
Motor HP (Qty)
1.34(1), 1.64(1) 3.90(1), 3.85(1) 3.90(1), 3.85(1)
3.90(1), 3.85(1)
3.90(2), 3.85(1)
Electrical Data
FLA
3.9
9.5
9.5
9.5
14.57
MCA
4.3
10.7
10.7
10.7
15.85
MFS
15
15
15
15
20
575-600/3/60 ACCD76022
ACCD76023
ACCD76024
ACCD76025
ACCD76026
Number of Fans
2
2
2
2
3
Fan RPM (Qty)
1450(1), 1570(1)1650(1), 1500(1) 1650(1), 1500(1) 1650(1), 1500(1) 1650(2), 1500(1)
Motor HP (Qty)
1.34(1), 1.64(1) 3.90(1), 3.85(1) 3.90(1), 3.85(1)
3.90(1), 3.85(1)
3.90(2), 3.85(1)
Electrical Data
FLA
3.4
8.0
8.0
8.0
12.3
MCA
37
9.0
9.0
9.0
13.4
MFS
15.0
15.0
15.0
15.0
15.0
Refrigerant Connections*
Hot Gas Line - in
1 1/8 OD
1 1/8 OD
1 3/8 OD
1 3/8 OD
1 5/8 OD
Liquid Line - in 
7/8 OD
7/8 OD
1 1/8 OD
1 1/8 OD
1 3/8 OD
Physical Data**
Dimensions -HxWxD in 35.5x32.75x76 48x108.5x48.25 48x108.5x48.25 48x108.5x48.25
48x155.5x48.25
Approximate Weight - lb.
240
455
495
555
835