Carrier 11-808-427-01 Manuale Utente

Pagina di 84
Installation 
 
 
10 
RTU Open 
 
Turn off the RTU Open's power. The controller reads the address each time you apply power to it. 
Using the rotary switches, set the MSB (SW1) (10's) switch to the tens digit of the address, and set the 
LSB (SW2)
 (1's) switch to the ones digit.  
EXAMPLE
  To set the RTU Open’s address to 01, point the arrow on the MSB (SW1) switch to 0 and the 
arrow on the LSB (SW2) switch to 1.   
 
Turn on the RTU Open's power. 
NOTE
  The factory default setting is "00" and must be changed to successfully install your RTU Open. 
  
  
 
To set the RTU Open's communications protocol and baud rate 
RTU Open's SW3 DIP switches are used to set the controller's protocol and baud rate. The protocol and speed 
selection is determined by the network on which the controller will be installed. For Carrier BACnet 
implementations, select MS/TP @ 76.8 k as follows: 
Power down the RTU Open. The controller reads the protocol and baud rate each time you apply power to 
it. 
Set SW3 DIP switches 1, 2, and 4 to On to configure the controller for BACnet MS/TP and 76.8 k baud.  
 
Power up the RTU Open. 
NOTE  
Other protocols and baud rates are available. See the RTU Open Integration Guide for additional 
instructions. 
  
 
 
Wiring the RTU Open to the MS/TP network 
The RTU Open communicates using BACnet on an MS/TP network segment communications at 9600 bps, 
19.2 kbps, 38.4 kbps, or 76.8 kbps.  
Wire the controllers on an MS/TP network segment in a daisy-chain configuration.