Service Test
 can be used to verify proper operation of compressors, heating stages, indoor fan, power 
exhaust fans, economizer, and dehumidification. It is highly recommended to use Service Test at initial 
system start-up and during troubleshooting. See Appendix A: Points/Properties (page 58) for more 
information. 
Service Test
 differs from normal operation as follows:  
• 
Outdoor air temperature limits for cooling circuits, economizer, and heating are ignored.  
• 
Normal compressor time guards and other staging delays are ignored.  
• 
Alarm statuses (except Fire and Safety Chain) are ignored, but all alarms and alerts are still broadcast on 
the network, if applicable.  
 
Service Test
 can be turned on or off from BACview, Field Assistant, or i-Vu. Select Default Value of Enable to 
turn on and Disable to turn off.  
 
NOTES
  
• 
Service Test
 mode is password-protected when accessed from a BACview.  
• 
Service Test
 allows testing of each controller output.  
• 
Binary Service Test
 functions are on when the Default Value is set to Enable and off when set to Disable. 
• 
The output of the Analog Service Test is controlled by the percentage (0-100%) entered into the Default 
Value
• 
It is recommended to return every Service Test variable to Disable or 0.00 after testing each function 
(unless that test variable must be active to test a subsequent function, as in Compressor 2 Test). 
• 
All outputs return to normal operation when Service Test is set to Disable. 
 
Service Test functions
 
• 
Use Fan Test to activate and deactivate the Supply Fan (BO - 1) output. Note that this output may enable 
simultaneously with other Service Test modes even with its Default Value set to Disable.  
• 
Use Compressor 1 Test to activate and deactivate the Compressor 1 (BO - 5) output. The Supply Fan 
output will be activated and deactivated in conjunction with this output. Leave Compressor 1 Test on 
Enable
 if Compressor 2 Test is required. 
• 
Use Compressor 2 Test to activate and deactivate the Compressor 2 (BO - 4) output. Always test the 
Compressor 1 output first. Compressor 1 Test output must be set to Enable for Compressor 2 Test to 
function. 
• 
Use the Reversing Valve Test to activate and deactivate the reversing valve (BO - 7) output. 
• 
Use the Dehumidification Test to activate and deactivate the Humidi-MiZer™ (BO - 6) output. The Supply 
Fan output will be activated and deactivated in conjunction with the Dehumidification Test output. 
• 
Use Heat 1Test to activate and deactivate the Heat 1 (BO - 3) output. The Supply Fan output is activated 
and deactivated in conjunction with the Heat 1Test output. 
• 
Use Heat 2Test to activate and deactivate the Heat 2 (BO - 2) output. The Supply Fan output is activated 
and deactivated in conjunction with the Heat 2Test output.