Sequence of Operation 
 
 
44 
RTU Open 
 
The cooling relays are controlled by the Cooling Control PID Loop and Cooling Stages Capacity algorithm. They 
calculate the desired number of stages needed to satisfy the space by comparing the Space Temperature to 
the: 
• 
Effective Occupied Cooling Setpoint 
when occupied 
• 
Effective Unoccupied Cooling Setpoint
 when unoccupied 
When the cooling algorithm preconditions have been met, the compressors are energized in stages, as 
applicable. Anti-recycle timers are employed to protect the equipment from short-cycling. There are fixed 
three-minute minimum on-times, and five-minute off-times for each compressor output. 
During compressor operation, the RTU Open may reduce the number of active stages if the rooftop supply air 
temperature falls below the Minimum Cooling SAT Setpoint. A compressor staged off in this fashion may be 
started again after the normal time-guard period has expired, if the Supply Air Temperature has increased 
above the Minimum Cooling SAT Setpoint. 
Compressor 2 Service Alarm Timer
 functions are available (one for each stage of compression). This function 
tracks the number of compressor run hours and generates an alarm when the accumulated runtime exceeds 
the threshold set by the adjustable compressor service alarm timers. 
  
 
Economizer 
The RTU Open provides an analog economizer output for rooftop units with economizer dampers. Economizer 
dampers may be used to provide free cooling and indoor air quality control when outside air conditions are 
suitable. 
The following conditions must be true for economizer operation: 
• 
The Outdoor Air Temperature is less than the Space Temperature and less than the Economizer High 
OAT Lockout Temp
 setpoint 
• 
The indoor fan has been on for at least 30 seconds 
• 
The unit has a valid Supply Air Temperature input 
• 
The unit has a valid Space Temperature input 
If any of the preceding conditions are not true, the economizer will be set to the Vent Dmpr Pos / DCV Min 
Pos
 setpoint. 
If all preceding conditions are true, the economizer PID loop will modulate the damper from the Vent Dmpr 
Pos / DCV Min Pos
 setpoint. 
The economizer moves to the Vent Dmpr Pos / DCV Min Pos setpoint if the SAT falls below the Minimum 
Cooling SAT
 (+ 5°F). 
  
 
Power Exhaust 
The RTU Open may enable and disable an exhaust fan, based on either the controller’s occupancy or its 
economizer damper position. 
If Continuous Occupied Exhaust is Yes, the Power Exhaust binary output (BO-8) is energized while theRTU 
Open is occupied and de-energized when unoccupied. 
If Continuous Occupied Exhaust is No, the Power Exhaust binary output (BO-8) is energized when the 
economizer damper output exceeds the Power Exhaust Setpoint value (default = 50%). The output remains 
energized until the economizer output falls below the Power Exhaust Setpoint value by a fixed hysteresis of 
10%.