RTU Open 
59 
 
Unit Configuration 
 
Navigation: 
i-Vu / Field Assistant: 
BACview: 
Properties 
Equipment 
Configuration  
Unit Configuration
 
HOME 
CONFIG  
 
UNIT
 
Point Name/Description
 
Default/Range
 
Fan Mode
Options: 
 – The supply fan's operating mode. 
Auto 
- The fan cycles on/off in conjunction with heating or cooling. 
Continuous 
- The fan runs continuously during occupancy & intermittently during 
unoccupied periods with heating or cooling. 
Always On
D: 
 - The fan runs continuously regardless of occupancy or calls for heating and 
cooling. 
R: 
Continuous 
Auto 
Continuous 
Always On 
Unit Start Delay
D: 
 – The amount of time the controller delays starting up after receiving a 
start command. 
R: 
5 sec 
0 to 30 sec 
Fan Off Delay
D: 
 – How long the supply fan runs after receiving a valid stop command. 
R: 
90 sec 
0 to 180 sec 
Minimum Cooling SAT
D: 
 – In cooling mode, the cooling outputs are controlled so that the 
supply air temperature does not drop below this value. 
R: 
50°F 
45 to 75°F 
Maximum Heating SAT
D: 
 – In heating mode, the heating outputs are controlled so the 
supply air temperature does not rise above this value. 
R: 
120°F 
85 to 150°F 
Vent Dmpr Pos / DCV Min Pos
D: 
 – The minimum outdoor air damper position maintained 
during occupied periods. 
R: 
50% Open 
0 to 100% Open 
DCV Max Vent Damper Pos
D: 
 – The maximum outdoor air damper position allowed while 
DCV is active. 
R: 
50% Open 
10 to 60% Open 
Supply Fan Service Alarm Timer
D: 
 – A Supply Fan Runtime alarm is generated when the 
supply fan run hours exceed this value. Set to 0 to disable. 
R: 
600 hr 
0 to 9999 hr 
Compressor 1 Service Alarm Timer
D: 
 – A Compressor 1 Runtime alarm is generated when 
the compressor 1 run hours exceed this value. Set to 0 to disable. 
R: 
0 hr 
0 to 9999 hr 
Compressor 2 Service Alarm Timer
D: 
 – A Compressor 2 Runtime alarm is generated when 
the compressor 2 run hours exceed this value. Set to 0 to disable. 
R: 
0 hr 
0 to 9999 hr 
Filter Service Alarm Timer
 – The amount of time the fan will run before generating a 
Filter Alarm
D: 
. Set to 0 to disable the alarm and reset accumulated fan hours. 
R: 
600 hr 
0 to 9999 hr 
Pushbutton Override
D: 
 – Enables or disables the use of a pushbutton override from a local 
space temperature sensor. 
R: 
Enable 
Disable/Enable 
Cooling Lockout Temp
D: 
 – The outdoor air temperature at which cooling is inhibited. 
R: 
45°F 
0 to 80°F 
Economizer High OAT Lockout
D: 
 – The outdoor air temperature at which economizer 
cooling is inhibited. 
R: 
75°F 
55 to 80°F