Carrier 11-808-427-01 Manuale Utente

Pagina di 84
 
 
 
RTU Open 
65 
 
 
Point Name/Description
 
Heating – 
(Occupied or Unoccupied, depending on mode) The current programmed Heating 
setpoint adjusted by any offset that may be in effect. 
Default/Range
 
R: 
0 to 120°F 
Cooling – 
(Occupied or Unoccupied, depending on mode) The current programmed Cooling 
R: 
setpoint adjusted by any offset that may be in effect. 
0 to 120°F 
Optimal Start
D: 
 – The earliest time, prior to occupancy, at which the Optimal Start function may 
begin to adjust the effective setpoints to achieve the occupied setpoints by the time scheduled 
occupancy begins. Enter 0 to disable Optimal Start. 
R: 
4 hr 
0 to 4 hr 
Occ Relative Humidity Setpoint
D: 
 – The percentage of relative humidity in the space during 
occupancy that will energize BO - 6 (Humidi-MiZer™). 
R: 
60%rh 
0 to Unoccupied 
RH Control 
Setpoint 
Unocc Relative Humidity Setpoint
D: 
 – The percentage of relative humidity in the space during the 
unoccupied time period that starts the unit and energizes BO - 6 (Humidi-MiZer™). 
R: 
95% 
30 to 100% 
DCV Max Ctrl Setpoint
D: 
 – The design difference between indoor and outdoor CO2 levels. 
R: 
650ppm 
0 to 9999 ppm 
Power Exhaust Setpoint
 - The outside air damper position at which the controller energizes the 
Power Exhaust relay. Configuration >Service Configuration > Economizer Exists must be set to 
Yes
, and Configuration >Service Configuration > Continuous Occupied Exhaust must be set to 
No
D: 
R: 
50% Open 
20 to 90% Open 
 
  
 
 
Alarm Configuration 
 
i-Vu / Field Assistant: 
Navigation:
 
BACview: 
Properties 
Equipment 
Configuration
 > 
Alarm Configuration  
  
HOME > CONFIG > ALARMS
 
Point Name/Description
 
Default/Range
 
 
  
Space Temperature Alarm
 
 
Occupied Alarm Hysteresis
D: 
 – This value is added to the occupied high effective 
setpoint and subtracted from the occupied low effective setpoint to establish the 
occupied high and low limits that the space temperature must exceed before an 
occupied SPT alarm is generated. The alarm returns to normal when the space 
temperature drops below the high effective setpoint or rises above the low effective 
setpoint. 
R: 
3°F 
0 to 20°F 
Alarm Delay (min/deg)
D: 
 – Determines the amount of delay before an occupied space 
temperature alarm is generated when the controller transitions to the occupied mode. 
The delay time equals this value multiplied by the difference between the sensor 
temperature and occupied alarm setpoint plus 15 minutes. 
R: 
10 minutes 
0 to 60 minutes 
Unoccupied Low SPT Alarm Limit
 –The value that the space temperature must drop 
below to generate a Space Temperature Alarm
D: 
 in the unoccupied mode. There is a 
fixed hysteresis of 1° F for return to normal. 
R: 
45°F 
-60 to 250°F