3.  1-Stage Compressor Units with Newer  
 
 
ECONWMt Economizers (See Note A)
1
st
 stage cooling set point is the setting (SP) input into 
the controller. Factory default is 77F (25C).  On a call 
for cooling the blower of the lead unit will come on 
immediately (if not already on – See Blower Operation), 
and the Stage 1 LED will blink for 10-seconds before 
going solid, at which time the lead unit Y1 cooling 
output turns on.  If the outdoor temperature and humidity 
conditions are below the set point of the economizer 
control the lead unit economizer will operate instead of 
the compressor.  If outdoor conditions are not acceptable 
for free cooling the compressor will automatically 
operate instead of the economizer. 
2
nd
 cooling set point is 4F (default setting, user selectable 
2-6F) warmer than Stage 1.  On a call for 2
nd
 Stage cooling 
the blower of the lag unit is turned on (if not already on – 
See Blower Operation), and the Stage 2 LED will blink for 
10-seconds before going solid, at which time the lag unit 
Y1 cooling output turns on.  If the outdoor temperature 
and humidity conditions are below the set point of the 
economizer control the lag unit economizer will operate 
instead of the compressor.  If outdoor conditions are 
not acceptable for free cooling the compressor will 
automatically operate instead of the economizer. 
3
rd
 cooling set point is 2F (default setting, user selectable 
2-3F) warmer than Stage 2.  On a call for 3
rd
 Stage 
cooling the lead unit economizer will continue to operate 
as long as outdoor conditions are acceptable, and the 
compressor will operate. 
4
th
 cooling set point is 2F (default setting, user selectable 
2-3F) warmer than Stage 3.  On a call for 4th Stage 
cooling the lag unit economizer will continue to operate 
as long as outdoor conditions are acceptable, and the 
compressor will operate.
4.  2-Stage Compressor Units with Newer   
 
ECONWMt  Economizers (See Note A)
1
st
 stage cooling set point is the setting (SP) input into 
the controller. Factory default is 77F (25C).  On a call 
for cooling the blower of the lead unit will come on 
immediately (if not already on – See Blower Operation), 
and the Stage 1 LED will blink for 10-seconds before 
going solid, at which time the lead unit Y1 cooling 
output turns on.  If the outdoor temperature and 
humidity conditions are below the set point of the 
economizer control the lead unit economizer will 
operate instead of the compressor.  If outdoor conditions 
are not acceptable for free cooling the compressor will 
automatically operate on compressor Stage 1 partial 
capacity instead of the economizer. 
2
nd
 cooling set point is 4F (default setting, user selectable 
2-6F) warmer than Stage 1.  On a call for 2
nd
 Stage 
cooling the blower of the lag unit is turned on (if not 
already on – See Blower Operation), and the Stage 2 
LED will blink for 10-seconds before going solid, at 
which time the lag unit Y1 cooling output turns on.  If 
the outdoor temperature and humidity conditions are 
below the set point of the economizer control the lag 
unit economizer will operate instead of the compressor. 
If outdoor conditions are not acceptable for free cooling 
the compressor will automatically operate on compressor 
Stage 1 partial capacity instead of the economizer. 
3
rd
 cooling set point is 2F (default setting, user selectable 
2-3F) warmer than Stage 2.  On a call for 3
rd
 Stage cooling 
the lead unit economizer will continue to operate as long 
as outdoor conditions are acceptable, and the compressor 
will operate on compressor Stage 1 partial capacity.  If 
outdoor conditions are not acceptable for free cooling the 
lead unit compressor will automatically be operating on 
compressor Stage 1 partial capacity and will go to Stage 2 
full capacity operation.  
4
th
 cooling set point is 2F (default setting, user selectable 
2-3F) warmer than Stage 3.  On a call for 4
th
 Stage cooling 
the lag unit economizer will continue to operate as long 
as outdoor conditions are acceptable, and the compressor 
will operate on compressor Stage 1 partial capacity.  If 
outdoor conditions are not acceptable for free cooling the 
lag unit compressor will automatically be operating on 
compressor Stage 1 partial capacity and will go to Stage 2 
full capacity operation.
cOOlInG OPeratInG seQuences FOr 
nOn-alternatInG leaD/leaD/laG/laG 
cOnFIGuratIOn
1.  2-Stage Compressor Units No Economizer
1
st
 stage cooling set point is the setting (SP) input into 
the controller. Factory default is 77F (25C).  On a call 
for cooling the blower of the lead unit will come on 
immediately (if not already on – See Blower Operation), 
and the Stage 1 LED will blink for 10-seconds before 
going solid, at which time the lead unit compressor will 
start in compressor Stage 1 partial capacity operation.
2
nd
 cooling set point is 4F (default setting, user selectable 
2-6F) warmer than Stage 1, at which time the lead unit 
compressor will switch to compressor Stage 2 full capacity.
3
rd
 cooling set point is 2F (default setting, user 
selectable 2-3F) warmer than Stage 2.  On a call for 3
rd
 
Stage cooling the blower of the lag unit will come on 
immediately (if not already on – See Blower Operation), 
and Stage 3 LED will blink for 10-seconds before going 
solid, and then the lag unit compressor will start in 
compressor Stage 1 partial capacity.  
4
th
 cooling set point is 2F (default setting, user selectable 
2-3F) warmer than Stage 3.  On a call for 4th Stage 
cooling the Stage 4 LED comes on solid (no delay), and 
the lag unit compressor will switch to compressor Stage 2 
full capacity operation.