Bryan Boilers 250 Manuale Utente

Pagina di 81
 
Date:  
8-4-2010 
 
Revision: 0 
 
Form:  
2396
 
Code Description 
Recommended 
Troubleshooting of Lockout Codes 
Code 
32-46 Internal 
fault: 
Safety Key 0 
through 14 
47 Flame 
Rod 
to 
ground leakage 
48 
Static flame (not 
flickering) 
 
41 
 
49 
24VAC voltage low/ 
high 
1. Check the Module and display connections. 
2. Check the Module power supply and make sure that both 
frequency, voltage and VA meet the specifications.  
50 Modulation 
fault 
51 Pump 
fault 
52 Motor 
tachometer 
fault 
Internal sub-system fault. 
1. Review alert messages for possible trends. 
2. Correct possible problems. 
53 AC 
inputs 
phase 
reversed 
1. Check the Module and display connections. 
2. Check the Module power supply and make sure that both 
frequency and voltagemeet the specifications. 
3. On 24Vac applications, assure that J4 terminal 10 and J8 
terminal 2 are connected together. 
54-57 RESERVED 
 
 
58 
Internal fault: HFS 
shorted to IAS 
59 
Internal Fault: Mux 
pin shorted 
60 
Internal Fault: HFS 
shorted to LFS 
Internal Fault. 
1. Reset Module. 
2. If fault repeats, replace module 
61 
Anti short cycle 
62  Fan speed not 
proved 
Will not be a lockout fault. Hold Only. 
63 
LCI OFF 
1. Check wiring and correct any faults. 
2. Check Interlocks connected to the LCI to assure proper 
function. 
3. Reset and sequence the module; monitor the LCI status. 
4. If code persists, replace the module 
64 
PII OFF 
1. Check wiring and correct any faults. 
2. Check Preignition Interlock switches to assure proper 
functioning. 
3. Check the valve operation. 
4. Reset and sequence the module; monitor the PII status. 
5. If code persists, replace the module. 
65 
Interrupted Airflow 
Switch OFF 
H or L 
66 
Interrupted Airflow 
Switch ON 
1. Check wiring and correct any possible shorts. 
2. Check airflow switches to assure proper functioning. 
3. Check the fan/blower operation. 
4. Reset and sequence the module; monitor the airflow status. 
5. If code persists, replace the module. 
H or L 
67 
ILK OFF 
1. Check wiring and correct any possible shorts. 
2. Check Interlock (ILK) switches to assure proper function. 
3. Verify voltage through the interlock string to the interlock input 
with a voltmeter. 
4. If steps 1-3 are correct and the fault persists, replace the 
module.