Figure 25. Gas/Air Test Panel.
Figure 26. Test Panel Valves.
panel are closed (see Figure 26).
5. 
Remove the two plugs from the + and – ports of 
the air orifice taps, thread hose barbs into the  
1/8" NPT connections, and attach the manometer 
pressure lines to the barbs. Be sure all 
connections are gas tight.
6. 
Switch on the appliance power switch located on 
the front of the unit.
7. 
The Brute Magnum will enter the start sequence. 
The blower and pump come on for pre-purge, 
then the ignitor warm-up sequence starts and 
after all safety devices are verified, the gas valve 
opens. If ignition doesn’t occur, check that there 
is proper gas supply. Wait 5 minutes and start the 
unit again.
8. 
Open air orifice test port valves.  Check air 
orifice differential at full fire, and make note of 
the differential.
9. 
Switch the Brute Magnum off.
10.  Close air orifice valves, remove the barbs and 
replace the plugs.  Make sure the connections are 
gas tight.
11.  Remove the two plugs from the + and – ports of 
the gas orifice taps, thread hose barbs into the  
1/8" NPT connections, and attach the manometer 
pressure lines to the barbs.  Be sure all 
connections are gas tight.
12.  Switch on the appliance power switch located on 
the front of the unit.
13.  The Brute Magnum will enter the start sequence.  
The blower and pump come on for pre-purge, 
then the ignitor warm-up sequence starts and 
after all safety devices are verified, the gas valve 
opens.
14.  Open gas orifice test port valves.  Check gas 
orifice differential at full fire, and make note of 
the differential.
15.  Close gas orifice valves, remove the barbs and 
replace the plugs.  Make sure the connections are 
gas tight.
16.  If gas and air orifice differentials match what is 
shown in Table 7, and do not differ from each 
other by more than 0.1" w.c., the unit is properly 
set up.  If not, consult, the factory.
17.  After placing the appliance in operation, the 
Burner Safety Shutoff Device must be tested. 
To test: 
 
(a)  Close gas shutoff valve with burner 
operating.
 
(b)  The flame will go out and blower will 
continue to run for the post purge cycle. 
One additional attempt to light will follow 
including pre-purge, ignitor on, valve/flame 
on and post purge. Ignition will not occur 
as the gas is off. The ignition control will 
lockout, and will have to be reset before the 
unit will operate.
Valve
Shown
Closed
Valve
Shown
Open