R7140G,L,M BURNER CONTROL MODULES
66-1153—03
8
* Check terminal 8 and 15.
If jumpered, ST7800A1031 (7 second purge).
If not jumpered, ST7800A1039 (30 second purge).
Mounting R7140 Relay Module 
Installing the Programmer (Fig. 3)
WARNING
Electrical Shock Hazard.
Can cause severe injury, death or property 
damage.
Disconnect power before installation to prevent 
electrical shock. More than one disconnect may be 
involved.
1. Open the master switch.
2. Make sure no subbase wiring is projecting out beyond 
the terminal blocks. Tuck in wiring against the back of 
the subbase so it does not interfere with the contacts.
3. Grasp the programmer chassis and engage the chassis 
hinge brackets with the pivot pins at the bottom of the 
subbase.
4. Swing the chassis inward until the spring connectors 
engage the knifeblade contacts. Push in until the 
contacts are fully engaged.
5. Tighten the chassis retaining screw securely.
6. Close the master switch to restore power.
Removing the Programmer
1. Open the master switch.
2. Loosen the chassis retaining screw.
3. Pull outward on the top of the chassis.
4. Disengage the chassis hinge brackets from the subbase 
pivot pins.
Fig. 3. Mounting the programmer on the subbase.
Table 6. J1/J2 Jumper Configuration for R4140M/PM720M.
Model
Purge Timer
Leave J1 & J2
Remove J1 and J2
R4140M1004/M1012
A1039
X
R4140M1020/M1038
A1047
X
R4140M1046/M1053
A1062
X
R4140M1079 (GP101)
A1062
X
R4140M1103/M1111
A1039
X
R4140M1145/M1152
A1047
X
R4140M1160/M1178
A1062
X
R4140M1186
A1047
X
R4140M1194
ST7800A1062
BC7000L1000 w/PM720M2002
ST7800A1062
X
BC7000L1000 w/PM720M2036
*
X
CHASSIS
RETAINING
SCREW
SPRING
CONNECTORS
KNIFE-BLADE
CONTACTS (20)
WIRING
SUBBASE
PIVOT PIN (2)
HINGE
BRACKET (2)
PROGRAMMER
CHASSIS
M22605