1.  The Crest is a high efficiency appliance that produces 
condensate.
2.  The rear of the boiler has a 1 inch (25.4 mm) stainless steel 
drain fitting and a 3/8 inch (9.8 mm) stainless steel vent line 
for connection to the condensate trap.  
3.  Connect the 1 inch (25.4 mm) fitting to the 1 inch (25.4 
mm) fitting on the condensate trap with the factory 
supplied silicone hose.  Secure the hose to the condensate 
trap and the boiler using the factory supplied hose clamps.
4.  Connect the 3/8 inch (9.8 mm) fitting to the 3/8 inch (9.8 
mm) fitting on the condensate trap (shipped loose) with 
the factory supplied silicone hose.  Secure the hose to the 
condensate trap and the boiler using the factory supplied 
hose clamps. 
5.  The condensate trap must be installed at the same level or 
below the boiler base.
6.  The condensate trap is sized for a 1" PVC outlet connection 
pipe.
7.  Plug the wiring connection from the condensate trap into 
the connector located on the back of the unit.
8.  Slope condensate tubing down and away from the boiler 
into a drain or condensate neutralizing filter.  Condensate 
from the Crest will be slightly acidic (typically with a pH 
from 3 to 5).  Install a neutralizing filter if required by local 
codes.
 
A  neutralizer  kit  (FIG.  8-1)  is  available  from  the  factory                  
(KIT30097). The neutralizer kit must be placed on a surface 
that is a minimum of 3 inches lower than the condensate 
trap with field supplied piping (vacuum break) installed 
between the condensate trap and the neutralizer kit.
Use materials approved by the authority 
having jurisdiction.  In the absence of 
other authority, PVC and CPVC pipe 
must comply with ASTM D1785 or D2845.  
Cement and primer must comply with 
ASME D2564 or F493.  For Canada use 
CSA or ULC certified PVC or CPVC pipe, 
fittings, and cement.
10.  A condensate removal pump is required if boiler is below 
the drain.  When installing a condensate pump, select one 
approved for use with condensing boilers and furnaces.  
The pump should have an overflow switch to prevent 
property damage from condensate spillage.  The switch 
should be wired to the auxiliary device proving switch 
terminals on the low voltage connection board.
 NOTICE
 NOTICE
To allow for proper drainage on large 
horizontal runs, a second line vent may 
be required and tubing size may need to 
increase to 1 inch (25 mm).
The condensate line must remain 
unobstructed, allowing free flow of 
condensate.  If condensate is allowed to 
freeze in the line or if the line is obstructed 
in any other manner, condensate can exit 
from the boiler tee, resulting in potential 
water damage to property.
CONDENSATE TRAP
SAME LEVEL OR BELOW
BOILER BASE
NEUTRALIZER KIT
(OPTIONAL)
3” MINIMUM BELOW
CONDENSATE TRAP
FLOOR DRAIN
OR DRAIN PAN
DETAIL
VACUUM
BREAK
IMG00174
Figure 8-1 Condensate Disposal
 
9.  Do not expose condensate line to freezing temperatures.