 U39 ULTIMATE Direct Vent Freestanding Gas Stove
Horizontal Venting with Two (2) 90
o
 Elbows
 Option      V 
         H + H1
     A) 
3'  Min.       2' Max.
     B) 
5'  Min.       3' Max.
     C) 
8'  Min.       4' Max.
     
With these options, maximum total 
pipe length is 30 feet with minimum 
of 8 feet total vertical and maximum 
4 feet total horizontal.
Please note minimum 1 foot 
between 90
o
 elbows is required.
INSTALLATION
One 90
o
 elbow = Two 45
o
 elbows.
Vertical Venting with Two (2) 90
o
 Elbows
 
Option  V 
    H 
   V1 
V + V1 
 
     A) 
1' Min.  1' Max.  1' Min.  2' Min. 
 
     B) 
1' Min.  2' Max.  2' Min.  3' Min. 
 
     C) 
2' Min.  3' Max.  2' Min.  4' Min. 
 
     D) 
2' Min.  4' Max.  2' Min.  4' Min. 
 
      
With these options, max. total pipe length is 30 
feet with min. of 4 feet total vertical and max. 4 feet 
total horizontal.
Please note min. 1 foot between 90
o
 elbows is 
required.
One 90
o
 elbow = Two 45
o
 elbows.
Vent restrictor position A (fully 
open), Refer to the "Venting Ar-
rangement" section.
Vent restrictor position A (fully open). Refer to 
the "Venting Arrangement" section.
Lengths do not include elbow 
indicated