FG37 Regency Rear Flued Room Sealed Freestanding Gas Heater
PLANNING YOUR FLUING INSTALLATION
INSTALLATION
FLUING
The Regency Room Sealed System (Horizontal
Termination Kit (946-110) and the Vertical Ter-
mination  with  the  Co-linear  Flex  System    in
combination with the REGENCY Room Sealed-
Rear Freestanding Gas Stoves (FG37-NG and
FG37-LPG) have been approved and listed as
Room  Sealed  heater  systems  by  Australian
Gas  Association.
The Horiz. Termination Kit (946-110) includes
everything required for a straight through the
wall installation, or add a 45
o
 elbow for a corner
installation.
 IMPORTANT
Read  all instructions carefully before starting
the installation. Failure to follow these instruc-
tions may create a fire or other safety hazard,
and will void the warranty. Be sure to check the
fluing  and  clearance  to  combustible  require-
ments  on  pages  6  to  9.  Consult  your  local
building codes before beginning installation.
The location of the termination cap must con-
form to the requirements in the Exterior Flue
Terminal Locations diagram on page 7.
FLUING
INSTALLATION
PRECAUTIONS
The  Regency  Room  Sealed  System  and  the
Vertical  Termination  with  the  Co-linear  Flex
System  are    engineered  products  that  have
been  designed  and  tested  for  use  with  the
FG37-NG, and FG37-LPG. The Regency war-
ranty will be voided and serious fire, health or
other safety hazards may result from any of the
following  actions:
1) Installation of any damaged Room Sealed
component
2) Unauthorized  modification  of  the  Room
Sealed System
3) Installation of any component part not man-
ufactured or approved by Regency  Indus-
tries Ltd.
4) Installation other than as instructed by Re-
gency Industries Ltd.
Warning: Always maintain required
clearances (air spaces) to nearby
combustibles to prevent a fire haz-
ard. Do not fill air spaces with insu-
lation.
The minimum clearance requirements between
the  outer  wall  of  the  flue  pipe  and  nearby
combustible  surfaces  is  30mm.  Be  sure  to
check the flue termination clearance require-
ments from decks, windows, soffits, gas reg-
ulators, air supply inlets and public walkways
as specified on page 7 and in your local building
codes.
The gas appliance and flue system
must be flued directly to the outside
of  the  building,  and  never  be  at-
tached to a chimney serving a sep-
arate solid fuel or gas-burning ap-
pliance.
Each Room Sealed gas appliance must use its
own separate flue system. Common flue sys-
tems are prohibited.
SAFETY
PRECAUTIONS  FOR
THE  INSTALLER
1) Wear  gloves  and  safety  glasses  for  pro-
tection.
2) Exercise extreme caution when using lad-
ders or on roof tops.
3) Be  aware  of  electrical  wiring  locations  in
walls  and  ceilings.
See  page  7  for  Exterior  Flue  Termination
requirements.
When planning your installation, it will be nec-
essary to select the proper length of flue pipe
for your particular requirements. Determine the
minimum  clearance  to  combustibles  from  the
rear of the unit to the wall. It is also important to
note the wall thickness. Before cutting the flue
hole through the wall ensure that ALL flue and
termination clearances (see page 7) will be met.
*If this is an outside corner, the minimum distance between the flue and the outside corner
is 12" (30cm). See "F" on the diagram on page 7.
NOTE:  Ensure  compliance  with  the  outside
flue  terminal  location  before  cutting  hole  as
both dimensions must be met.
For corner installation, Restrictor must
be set at 1-1/4" (32mm) open.
For straight rear installation, Restric-
tor must be set at 1-1/8" (29mm) open.