Lightolier FBP30T Dépliant
631 Airport Road, Fall River, MA 02720 • (508) 679-8131 • Fax (508) 674-4710
We reserve the right to change details of design, materials and finish.
www.lightolier.com © 2008 Philips Group • D0708
We reserve the right to change details of design, materials and finish.
www.lightolier.com © 2008 Philips Group • D0708
Job Information
Type:
Job Name:
Cat. No.:
Lamp(s):
Notes:
FBP Series Fluorescent Emergency Ballast
FBP30T
Page 1 of 1
One or Two Lamp Operation 3,500 Lumens
Lightolier is a Philips group brand
Nickel Cadmium Battery
The FBP Series quickly converts standard fluorescent luminaires into emergency luminaires.
16.3”
(41.4 cm)
5.6”
(14.2 cm)
1.7”
(4.3 cm)
Features
1. Lamp Operation: Operates the following lamp types: T8 linear fluores-
cent, T12 linear fluorescent, T9 circline, T12 U-bent, T5 long compact fluo-
rescent, compact 4-pin fluorescent. See Lamp Operation and Performance
table for specific lamp performance and operation.
rescent, compact 4-pin fluorescent. See Lamp Operation and Performance
table for specific lamp performance and operation.
2. Illumination: Provides 90 minutes of emergency illumination, and produc-
es a maximum of 3,500 lumens initial emergency light output. Can be used
with most 17w to 215w (2’ - 8’) T8, T10 or T12 fluorescent lamps without
integral starters including U-shaped, HO, VHO, circline, energy saving, and
4 pin compacts. It is also compatible with most 1, 2, 3 and 4-lamp elec-
tronic, standard, energy saving and dimming AC ballasts, including those
with end of life detection.
with most 17w to 215w (2’ - 8’) T8, T10 or T12 fluorescent lamps without
integral starters including U-shaped, HO, VHO, circline, energy saving, and
4 pin compacts. It is also compatible with most 1, 2, 3 and 4-lamp elec-
tronic, standard, energy saving and dimming AC ballasts, including those
with end of life detection.
3. Housing: Constructed of 20 gauge steel with a white high temperature
powder coat paint finish. Slim housing allows for wireway channel mount-
ing on most recessed luminaires.
ing on most recessed luminaires.
4. Electronics: 120/277 VAC dual voltage input with surge-protected, solid-
state circuitry. Charging system is complete with AC indicator lamp and
test switch.
test switch.
5. Battery: Maintenance free, sealed nickel cadmium battery has an esti-
mated service life of 10 years, and an operating temperature range of 32°F
(0°C) to 131°F (55°C).
(0°C) to 131°F (55°C).
6. Input Power Requirements: 8 watts max.
7. Warranty: Electronics: 5 years; Battery: 5 years.
7. Warranty: Electronics: 5 years; Battery: 5 years.
Code Compliance
UL 924 listed.
Options
EX = Special Input Transformer for 220 VAC/50 Hz, 240 VAC/50Hz. Contact
factory for other input voltages and frequencies.
DL = UL Damp Location Listing
factory for other input voltages and frequencies.
DL = UL Damp Location Listing
Accessories
CCAPS = Wire bundle cover for mounting external to luminaire.
RTS = Single gang aluminum faceplate pre-drilled to accommodate remote
installation of test switch and pilot light.
RTS = Single gang aluminum faceplate pre-drilled to accommodate remote
installation of test switch and pilot light.
Complete Fixture consists of ballast unit. Select options and accessories below.
Model #
Max. Lumens
Lamp Operation
FBP30T
3,500
One or Two
Lamp Operation and Performance
Non-Emer. Emer. Op.
Op. Max.
Max.
Emer.
Lamp
Watt.
Non-Emer.
Lumen
Lumen
Lamp
Type
Type
Base
Output
Output
Operation
F40/34T12
34-40 G13/Med Bi-Pin
2900
3000
One or Two
F40T12/U
40
G13/Med Bi-Pin
3100
3000
One or Two
F48T12HO
60
R17D/Recessed
4050
3000
One
F96T12HO/VHO 95-215 R17D/Recessed 8800/15200
3000
One
F25T8
25
G13/Med Bi-Pin
2200
2500
One or Two
F32T8
32
G13/Med Bi-Pin
3000
3000
One or Two
F32T8/U
32
G13/Med Bi-Pin
2700
3000
One or Two
F40T8
40
G13/Med Bi-Pin
3700
2500
One
F96T8
59
FA8/Single-Pin
5700
3000
One
F39/36BX
39
2G11/4--Pin
2900
3000
One or Two
F40/30BX
40
2G11/4--Pin
3200
2000
One
F42TBXT4
42
GX24Q-4P
3200
3200
One or Two
Notes:
1. Maximum non-emergency lumen output can vary based on lamp manufacturer, ambient operating
1. Maximum non-emergency lumen output can vary based on lamp manufacturer, ambient operating
temperature, and ballast manufacturer.
2. Maximum emergency lumen output is based on total output of one or two lamps, and can vary
based on lamp manufacturer and ambient operating temperature.
3. Maximum emergency lumen output is supported for a full 90 minutes of operation.
4. Consult factory for compatibility, operation and performance of lamp types not listed.
4. Consult factory for compatibility, operation and performance of lamp types not listed.