Lightolier FAEM3 Manuale Utente

Pagina di 4
READ AND UNDERSTAND THESE INSTRUCTIONS BEFORE INSTALLING FIXTURE
This fixture is intended for installation in accordance with the National Electrical Code and local 
regulations. To assure full compliance with local codes and regulations, check with your local electrical
inspector before installation. To prevent electrical shock, turn off electricity at fuse box before proceeding.
Retain these instructions for maintenance reference.
INSTRUCTION SHEET NO.
IS:FAEM3
C0506
Page 1 of 4
IMPORTANT SAFEGUARDS
READ AND FOLLOW ALL SAFETY INSTRUCTIONS
WHEN USING ELECTRICAL EQUIPMENT, BASIC SAFETY PRECAUTIONS SHOULD BE FOLLOWED INCLUDING THE FOLLOWING:
1. TURN OFF AC POWER BEFORE PROCEEDING.
2. DO NOT INSTALL INSULATION WITHIN 3 INCHES OF FIXTURE SIDES OR WIRING COMPARTMENT, NOR ABOVE FIX-
TURE IN SUCH A MANNER AS TO ENTRAP HEAT.
3. BE SURE ALL ELECTRICAL CONNECTIONS ARE COMPLETE AND THE JUNCTION BOX IS CLOSED BEFORE INVERTER
CONNECTORS (LOCATED IN THE SWITCH/INDICATOR LIGHT BOX) ARE CONNECTED.
4. DO NOT USE OUTDOORS.
5. DO NOT LET POWER SUPPLY CORDS TOUCH HOT SURFACES.
6. DO NOT MOUNT NEAR GAS OR ELECTRICAL HEATERS.
7. USE CAUTION WHEN SERVICING BATTERIES. CONTAINS NICKEL-CADMIUM RECHARGEABLE BATTERY. MUST BE
RECYCLED OR DISPOSED OF PROPERLY. DO NOT SHORT CIRCUIT; MAY CAUSE BURNS. 
8. EQUIPMENT SHOULD BE MOUNTED IN LOCATIONS AND AT A HEIGHT WHERE IT WILL NOT READILY BE SUBJECT TO
TAMPERING BY UNAUTHORIZED PERSONNEL.
9. THE USE OF ACCESSORY EQUIPMENT NOT RECOMMENDED BY THE MANUFACTURER MAY CAUSE AN UNSAFE 
CONDITION.
10. DO NOT USE THIS EQUIPMENT FOR OTHER THAN INTENDED USE.
11. THIS UNIT HAS MORE THAN ONE POWER SUPPLY CONNECTION POINT. TO REDUCE THE RISK OF ELECTRICAL SHOCK,
DISCONNECT BOTH NORMAL AND EMERGENCY POWER SUPPLIES BEFORE SERVICING.
12. BEFORE SERVICING TO PREVENT ELECTRICAL SHOCK, DISCONNECT THE INVERTER CONNECTORS OF THE EMER-
GENCY BATTERY PACK (LOCATED IN THE SWITCH/INDICATOR LIGHT BOX). MAKE CERTAIN THAT THE SWITCHED (IF
THE FIXTURE IS SWITCHED) AND THE UNSWITCHED LINE TO THE EMERGENCY BATTERY PACK ARE TURNED OFF AT
THE FUSE BOX. SERVICING SHOULD BE PERFORMED BY QUALIFIED SERVICE PERSONNEL ONLY.
13. BEFORE ANY INSTALLATION, MAKE SURE TO CHECK THE COMPATIBILITY MATRIX BELOW BEFORE INSTALLATION.
INCORRECT MATCHING MAY CAUSE ELECTRICAL SHOCK AND DAMAGE TO BALLASTS AND LAMPS. FOR USE WITH
NON-DIMMING (U SERIES) AND DIMMING (J-SERIES) FRAME-IN KITS. 
Installation of Compact Fluorescent Emergency Ballast Accessory FAEM3E to 
Standard Calculite Four-Pin Electronic Compact Fluorescent Lamp Frame-In Kit
SAVE THESE INSTRUCTIONS
LIGHTOLIER a GENLYTE THOMAS  company.
631 Airport Road, Fall River, MA  02720
®
Emergency Ballast
Lamp
Wattage
Compatible Ballast
13W
Quad Tube 4-Pin
18W
FA-EM3E
26W
Triple Tube 4-Pin
18W
26W
32W
42W
Electroninc Non-Dimming 
Advance Mark 7 and Mark 10 (Dimming)
Lutron compact SE, Hi-Lume, 
TU-Wire (Dimming)