Schneider Electric iEM3200 Manuale Utente

Pagina di 112
iEM3100 / iEM3200 / iEM3300 series user manual 
Overview
DOCA0005EN-04
13
Typical applications
This range is a cost effective solution to monitor feeder circuits. These meters can monitor energy 
consumption by usage, by zone or by feeder in the cabinet. They can be used to monitor feeders in a 
main switchboard or to monitor the main in a distribution cabinet.
iEM31•• and iEM33•• series
iEM32•• series
Typical applications
The following table presents some of the functions of the different meters, the advantages and main 
applications.
Overload alarm
Communications
Modbus
LonWorks
M-Bus
BACnet
MID compliant
Width (18 mm module in DIN rail mounting)
5
5
5
5
5
5
5
5
Function
iEM3200
iEM3210
iEM3215
iEM3235
iEM3250
iEM3255
iEM3265
iEM3275
Functions
Advantages
Can directly measure feeders up to:
iEM31••: 63 A 
iEM33••: 125 A
Embedded current transformers (CTs)
Saves installation time and space in the cabinet
No wiring to manage
Clear distribution network
Adapted to be installed with Acti9 iC65 (iEM31••) or Acti9 C120 
(iEM33••) circuit breakers
Can be used in three-phase systems with or without neutral
Can be used for single-phase multi-circuit monitoring
3 single feeders can be monitored with a single meter
Functions
Advantages
CT and VT connection
Can be used in low or medium voltage applications
Flexible configuration
Can be adapted to any distribution network with or without neutral
Functions
Advantages
Applications
Meter
Total and partial energy counters Energy usage monitoring
Sub-billing management
Metering applications
All
Internal clock
Saves the date and time of last reset
Provides the timestamp of the last reset of the 
partial energy accumulation
All (except iEM3100 / 
iEM3200 / iEM3300)
Pulse output with a configurable 
pulse weight of up to 1 pulse per 
1 Wh
Collect pulses from the meter with a Smartlink 
system, PLC or any basic acquisition system
Remote monitoring of energy consumption
Integrate the meter in to a system monitoring of 
a large number of devices
iEM3110 / iEM3310 / 
iEM3210
Manages up to four tariffs, 
controlled by the digital input(s), 
internal clock or communications 
(depending on meter model)
Categorize energy consumption into On Peak and Off 
Peak, working days and weekends, or by different 
electricity sources (for example, from the utility and 
an electrical generator)
Energy demand management
Sub-billing management
Identification of local energy consumption 
behavior by zone, by usage or by feeder
iEM3115 / iEM3135 / 
iEM3155 / iEM3165 / 
iEM3175
iEM3215 / iEM3235 / 
iEM3255 / iEM3265 / 
iEM3275
iEM3335 / iEM3355 / 
iEM3365 / iEM3375
Measures essential electrical 
parameters like current, average 
voltage and total power.
Instantaneous measurements help you monitor the 
imbalance between phases.
Total power allows you to monitor the feeder load 
level.
Monitoring of feeders or any sub-cabinet
iEM3135 / iEM3155 / 
iEM3165 / iEM3175
iEM3235 / iEM3255 / 
iEM3265 / iEM3275
iEM3335 / iEM3355 / 
iEM3365 / iEM3375