Front panel display and meter setup
DOCA0005EN-04
45
Configuration menus for iEM3200 / iEM3210 / iEM3215
A
iEM3210 / iEM3215
B
iEM3210
C
iEM3215
Wiring
Type
CT
CT Ratio
CT Secondary
CT Primary
Frequency
Frequency
Date
Date
Time
Time
Disable
by Internal Clock
Multi Tariffs
Control mode
Schedule
by 2 Tariffs
by 3 Tariffs
by 4 Tariffs
by Digital Input
by Communications
Pulse Output
Pulse Constant
Contrast
Contrast
Password
Password
Reset Config
Reset Config
Pulse Width
Section
Parameter
Options
Description
Wiring
Type
3PH3W
3PH4W
1PH2W L-N
1PH2W L-L
1PH3W L-L-N
3PH4W
1PH2W L-N
1PH2W L-L
1PH3W L-L-N
Select the power system type the meter is wired to.
CT
3CTs on I1, I2, I3
1 CT on I1
2 CTs on I1, I3
1 CT on I1
2 CTs on I1, I3
Define how many current transformers (CT) are connected to the meter and
which terminals they are connected to.
which terminals they are connected to.
CT Ratio
CT Secondary
1
5
5
Select the size of the CT secondary, in Amps.
CT Primary
1 - 32767
Enter the size of the CT primary, in Amps.
Frequency
Frequency
50
60
60
Select the frequency of the electrical power system, in Hz.
Date (iEM3210 / iEM3215)
Date
DD-MMM-YYYY
Set the current date using the specified format.
Time (iEM3210 / iEM3215)
Time
hh:mm
Set the time using the 24-hour format.
Pulse Output (iEM3210)
Pulse Constant
(imp/kWh)
(imp/kWh)
0.01
0.1
1
10
100
500
0.1
1
10
100
500
Set the pulses per kWh for the pulse output.
Pulse Width
(ms)
(ms)
50
100
200
300
100
200
300
Set the pulse width (ON time).