Schneider Electric iEM3200 Manuale Utente

Pagina di 112
54
DOCA0005EN-04
Communications via Modbus RS-485
iEM3100 / iEM3200 / iEM3300 series user manual
Command list
Set Date/Time
Set Wiring
Command 
Number
Action
(R/W)
Size
Type
Unit
Range
Description
1003
W
1
UInt16
(Reserved)
W
1
UInt16
2000–2099
Year
W
1
UInt16
1–12
Month
W
1
UInt16
1–31
Day
W
1
UInt16
23
Hour
W
1
UInt16
0–59
Minute
W
1
UInt16
0–59
Second
W
1
UInt16
(Reserved)
Command 
Number
Action
(R/W)
Size
Type
Unit
Range
Description
2000
W
1
UInt16
(Reserved)
W
1
UInt16
(Reserved)
W
1
UInt16
(Reserved)
W
1
UInt16
0, 1, 2, 3, 11,13
Power System Configuration
0 = 1PH2W L-N
1 = 1PH2W L-L
2 = 1PH3W L-L-N
3 = 3PH3W
11 = 3PH4W
13 = 1PH4W L-N
W
1
UInt16
Hz
50, 60
Nominal Frequency
W
2
Float32
(Reserved)
W
2
Float32
(Reserved)
W
2
Float32
(Reserved)
W
1
UInt16
(Reserved)
W
1
UInt16
(Reserved)
W
2
Float32
V
VT Secondary–
1000000.0
VT Primary
NOTE: For iEM3250 / iEM3255. Reserved by iEM3150 / iEM3155 / 
iEM3350 / iEM3355
W
1
UInt16
V
100, 110, 115, 120
VT Secondary
NOTE: For iEM3250 / iEM3255. Reserved by iEM3150 / iEM3155 / 
iEM3350 / iEM3355
W
1
UInt16
1, 2, 3
Number of CTs
NOTE: For iEM3250 / iEM3255. Reserved by iEM3150 / iEM3155 / 
iEM3350 / iEM3355
W
1
UInt16
A
1–32767
CT Primary
NOTE: For iEM3250 / iEM3255. Reserved by iEM3150 / iEM3155 / 
iEM3350 / iEM3355
W
1
UInt16
A
1, 5
CT Secondary
NOTE: For iEM3250 / iEM3255. Reserved by iEM3150 / iEM3155 / 
iEM3350 / iEM3355
W
1
UInt16
(Reserved)
W
1
UInt16
(Reserved)
W
1
UInt16
(Reserved)
W
1
UInt16
(Reserved)
W
1
UInt16
0, 1, 2
VT Connection type:
0 = Direct Connect
1 = 3PH3W (2 VTs)
2 = 3PH4W (3 VTs)
NOTE: For iEM3250 / iEM3255. Reserved by iEM3150 / iEM3155 / 
iEM3350 / iEM3355