Schneider Electric iEM3200 Manuale Utente

Pagina di 112
58
DOCA0005EN-04
Communications via Modbus RS-485
iEM3100 / iEM3200 / iEM3300 series user manual
Energy Pulse Output Setup (iEM3155 / iEM3255 / iEM3355)
Command Interface
Communication 
Input Metering Setup (iEM3155 / iEM3255 / iEM3355)
2031
R/WC
1
UInt16
A
CT Secondary
Not applicable for iEM3150 / iEM3155 / iEM3350 / iEM3355
2036
R/WC
1
UInt16
VT Connection Type
0 = Direct Connect
1 = 3PH3W (2 VTs)
2 = 3PH4W (3 VTs)
Not applicable for iEM3150 / iEM3155 / iEM3350 / iEM3355
Register 
Address
Action
(R/W/WC)
Size
Type
Units
Description
2129
R/WC
1
UInt16
Millisecond
Energy Pulse Duration
2131
R/WC
1
UInt16
Digital Output Association
0 = Disable
1 = DO1 enable for active energy pulse output
2132
R/WC
2
Float32
pulse/kWh
Pulse Weight
Register 
Address
Action
(R/W/WC)
Size
Type
Units
Description
5250
R/W
1
UInt16
Requested Command
5252
R/W
1
UInt16
Command Parameter 001
5374
R/W
1
UInt16
Command Parameter 123
5375
R
1
UInt16
Command Status
5376
R
1
UInt16
 Command Result codes:
0 = Valid Operation
3000 = Invalid Command
3001 = Invalid Parameter
3002 = Invalid Number of Parameters
3007 = Operation Not Performed
5377
R/W
1
UInt16
Command Data 001
5499
R
1
UInt16
Command Data 123
Register 
Address
Action
(R/W/WC)
Size
Type
Units
Description
6500
R
1
UInt16
Protocol
0 = Modbus
6501
R/WC
1
UInt16
Address
6502
R/WC
1
UInt16
Baud Rate:
0 = 9600 
1 = 19 200
2 = 38 400
6503
R/WC
1
UInt16
Parity:
0 = Even 
1 = Odd 
2 = None
NOTE: number of stop bits = 1
Register 
Address
Action
(R/W/WC)
Size
Type
Units
Description
7032
R/WC
20
UTF8
Label
Register 
Address
Action
(R/W/WC)
Size
Type
Units
Description