See “Echelon LonMaker plug-in for data display and meter configuration” on page 71 for 
instructions on using the LNS plug-in to configure the meter.
Resets
Meter configuration properties
You can configure the meter using the configuration properties listed in this section. However, it is 
recommended that you use the Echelon LonMaker plug-in if you are configuring the meter using 
LonWorks communications.
NOTE: If Com. Protection is enabled, you may receive an error response when you try to configure 
the meter over communications.
Related topics
See “Echelon LonMaker plug-in for data display and meter configuration” on page 71 for 
instructions on using the LNS plug-in to configure the device.
Date/time setup
nvoAlmUnAckState
SNVT_count
Acknowledgement status (only Bit 1 is used):
0 = historic alarm is acknowledged by the user
1 = historic alarm is unacknowledged by the user
nvoAlmLastTime
SNVT_time_stamp
Timestamp of last alarm (DD/MM/YYYY hh:mm:ss)
nvoAlmLastValue
SNVT_power_f
Value at last alarm
nciAlmEnable
SNVT_count
Overload alarm configuration:
0 = disabled
1 = enabled
nciAlmPkUpSetPt
SNVT_power_f
Active power alarm pickup setpoint in kW
Network variable label SNVT / UCPT type
Description
Network variable label
Type
Description
Action
nciRstPartEnergy
SNVT_switch
Resets all partial energy accumulators to 0:
Partial active energy import (nvoPartialkWh, nvoPartialWh)
Partial reactive energy import (nvoPartialkVARh, nvoPartialVARh)
Rate A active energy import (nvoTariffAkWh, nvoTariffAWh)
Rate B active energy import (nvoTariffBkWh, nvoTariffBWh)
Rate C active energy import (nvoTariffCkWh, nvoTariffCWh)
Rate D active energy import (nvoTariffDkWh, nvoTariffDWh)
Active energy import phase 1 (nvoPh1kWh, nvoPh1Wh)
Active energy import phase 2 (nvoPh2kWh, nvoPh2Wh)
Active energy import phase 3 (nvoPh3kWh, nvoPh3Wh)
To reset, set the state field to 1.
nciRstInMeterAcc
SNVT_swtich
Resets input metering accumulation (nvoInMeterAcc) to 0
To reset, set the state field to 1. 
Function profile UCPT
Struct Members
Range / options
nciCfgDateTime
UCPTDateTime
year
2000 - 2099
month
1 - 12
day
1 - 31
hour
0 - 23
minute
0 - 59
second
0 - 59