Communications via LonWorks
DOCA0005EN-04
71
Echelon LonMaker plug-in for data display and meter configuration
The information in this section assumes that you have an advanced understanding of system 
administration using Echelon LonMaker.
The LonMaker plug-in provides a graphical user interface where you can view meter values and 
configure meter settings. Once you install and register the plug-in with LonMaker, it opens instead of 
the default LonMaker browser when you browse the meter in LonMaker.
To add devices to LonMaker, you need access to the device service pin when commissioning the 
device or your need the device Neuron ID recorded in an accessible location.
Related topics
Refer to http://www.echelon.com/products/tools/integration/lonmaker/ and the LonMaker 
documentation for more information on using LonMaker.
Installing and registering the LonMaker plug-in
Before you install the plug-in:
Download the plug-in and XIF file for your device from www.schneider-electric.com or contact your 
sales representative to obtain these files. 
Make sure Echelon LonMaker is closed.
1. Navigate to the location where you saved the plug-in. Extract the files if they are in a .zip file. 
2. Double-click setup.exe. A welcome screen appears. Click Next.
3. Select the installation folder where you want to install the plug-in. Click Browse if you want to 
select a different location. Click Next. A confirmation screen appears.
4. Click Next to begin the installation. 
NOTE: If LonMaker is open, a message appears instructing you to close LonMaker and restart the 
plug-in installation.
nciAllEnergy
SCPTminSendTime
Floating-point energy values:
nvoTotWhImp
nvoTotWhExp
nvoTotVARhImp
nvoTotVARhExp
nvoPartialWh
nvoPartialVARh
nvoPh1Wh
nvoPh2Wh
nvoPh3Wh
nvoTariffAWh
nvoTariffBWh
nvoTariffCWh
nvoTariffDWh
The minimum interval, in seconds, between consecutive transmissions of the 
listed variable values to the network.
No updates to the value of the applicable variables are sent over the network 
until the minimum interval has elapsed, regardless of whether or not the value of 
the variable has changed.
After an update is sent, the counter is reset to 0.
nciAllPower
SCPTminSendTime
nvoActPowerPh1
nvoActPowerPh2
nvoActPowerPh3
nvoActPowerSum
nvoRctPowerSum
nvoAppPowerSum
nciAllVoltage
SCPTminSendTime
nvoVoltsL1N
nvoVoltsL2N
nvoVoltsL3N
nvoVoltsLNAvg
nvoVoltsL1L2
nvoVoltsL2L3
nvoVoltsL3L1
nvoVoltsLLAvg
nciAllCurrent
SCPTminSendTime
nvoCurrentPh1
nvoCurrentPh2
nvoCurrentPh3
nvoCurrentAvg
nciAllPowerFactor
SCPTminSendTime
nvoAvgPwrFactor
nciFrequency
SCPTminSendTime
nvoFrequency
nci variable
UCPTs/SCPTs
Applies to...
Description