Schneider Electric iEM3200 Manuale Utente
![Schneider Electric](https://files.manualsbrain.com/attachments/984caf1d286e5e02d462a79fde1bf5fead2d9a5f/common/fit/150/50/91444bf287fb583af13341fc3281cd3c182bc046c845d04ce567acdbd94e/brand_logo.gif)
82
DOCA0005EN-04
Communications via M-Bus
iEM3100 / iEM3200 / iEM3300 series user manual
Alarm status information
NOTE: E denotes the extension bit; the hex value assumes E = 0.
Telegram information for meter configuration
You can use the information provided in this section to write to the meter using a SND_UD function.
NOTE: If Com. Protection is enabled, you may receive an error response when you try to configure
the meter over communications.
the meter over communications.
You can also configure the meter using the M-Bus tool available from www.schneider-electric.com.
Supported VIFE codes for meter configuration
NOTE: E denotes the extension bit; the hex value assumes E = 0.
Related topics
•
See “Configuration mode menus” on page 40 for information on enabling and disabling
Com. Protection.
Com. Protection.
•
See “M-Bus tool for data display and meter configuration” on page 85 for information on the
M-Bus tool.
M-Bus tool.
05
—
—
E010 1110
2E
Pulse weight of the digital output
NOTE: This information only applies if the digital output mode is set to
energy pulsing.
NOTE: This information only applies if the digital output mode is set to
energy pulsing.
03
E001 1010
1A
—
—
Digital output control mode
2 = for Alarm
3 = for Pulse (kWh)
0xFFFF = Disabled
2 = for Alarm
3 = for Pulse (kWh)
0xFFFF = Disabled
03
—
—
E010 1101
2D
Digital output association with energy pulsing:
0 = Digital output disabled
1 = for Pulse (digital output is associated with active energy pulse output)
0 = Digital output disabled
1 = for Pulse (digital output is associated with active energy pulse output)
02
—
—
E011 0110
36
Digital output association with overload alarm:
0x0000 = digital output disabled
0x0100 = for Alarm (digital output is associated with the overload alarm)
0x0000 = digital output disabled
0x0100 = for Alarm (digital output is associated with the overload alarm)
Data format
Primary VIFE
Manufacturer-specific VIFE
Description
bin
hex
bin
hex
Data format Primary VIF
Manufacturer-specific VIFE
Description
bin hex
02
—
E011 0111
37
Alarm status:
0x0000 = Alarm is inactive
0x0100 = Alarm is active
0x0000 = Alarm is inactive
0x0100 = Alarm is active
02
—
E011 1000
38
Acknowledgement status:
0x0000 = historic alarm is acknowledged by the user
0x0100 = historic alarm is unacknowledged by the user
0x0000 = historic alarm is acknowledged by the user
0x0100 = historic alarm is unacknowledged by the user
04
ED
E011 1001
39
Timestamp of last alarm (DD/MM/YYYY hh:mm:ss)
05
—
E011 1010
3A
Value at last alarm
02
—
E011 0100
34
Overload alarm configuration:
0x0000 = disabled
0x0100 = enabled
0x0000 = disabled
0x0100 = enabled
05
—
E011 0101
35
The pickup setpoint in kW for the overload alarm
VIFE code
Action
Description
bin hex
E000 0000
00
Write and replace
Replaces the old value with the new value.
E000 0111
07
Clear
Resets an accumulated value to 0 (zero).