Schneider Electric iEM3200 Manuale Utente

Pagina di 112
iEM3100 / iEM3200 / iEM3300 series user manual 
Communications via M-Bus
DOCA0005EN-04
87
Configuring the meter using the M-Bus tool
1. Select Setup > Config to switch to configuration mode.
2. Set the values that you want to change then click Send for that value or section. For example, to 
change the nominal frequency, select a different value from the list then click Send in Set Wiring
Some values may be unavailable based on existing settings. 
NOTE: If Com. Protection is enabled, you may receive a message that the configuration failed. 
Use the HMI to either: 1) configure the meter, or 2) disable Com. Protection then configure the 
meter using the tool.
The configuration screen has the following sections:
RMS Measure
This tab provides power, current, and voltage values as well as frequency and power factor information.
Meter Status
This tab provides information on the settings and status of the digital input, digital outputs and alarms as 
well as existing power system settings.
Section
Description
Set Wiring
Configure power system settings (for example, power system configuration and nominal 
frequency).
Set Digital Input
Set the digital input mode and pulse constant.
Set Digital Output
Enable / disable the digital output and set the control mode, pulse weight and duration.
Set Multi Tariff
Disable the Multi Tariff feature or set the control mode to by Communication and set the active tariff 
if the control mode is set to by Communication.
Set Power Alarm
Enable / disable to the overload alarm, enter the setpoint, and acknowledge alarms.
Reset
Reset partial energy and input metering accumulations.
Set Date Time
Set the date and time or send a time synchronization signal to set the meter to the computer time.
Set Baudrate
Set the baud rate.
Set Address
Set the meter address.
Tab name
Description