Communications via BACnet
DOCA0005EN-04
91
Make sure that the Mac Address is unique on the serial loop and the Device ID is unique in your 
BACnet network.
Communications LED indicator for BACnet meters 
The LED indicates the status of the meter’s communications with the network.
Change of Value (COV) subscriptions
The meter supports up to 14 COV subscriptions. You can add COV subscriptions to Analog Input and 
Binary Input objects using your BACnet-compatible software.
Related topics
BACnet object and property information
The following sections outline the supported objects and properties available on the meter.
Device object
The following table outlines the properties of the Device object, whether a property is read-only or 
read-write, and if the value of the property is stored in the meter’s non-volatile onboard memory.
LED state
Description
The LED is off
Communication is not active.
The LED is flashing
Communication is active.
NOTE: The LED flashes even if there is a communications error.
Device object property
R/W
Stored
Possible values
Description
Object_Identifier
R
configurable
The unique device ID number for the meter, in the format of <device, #>.
NOTE: You must use the front panel to configure the device ID number.
Object_Name
R/W
configurable
A configurable name for the meter.
The meter ships from the factory with a name of <model name>_<serial number> 
(for example, iEM3265_0000000000).
Object_Type
R
Device
The object type for the meter
System_Status
R
Operational
This value of this property is always Operational.
Vendor_Name
R
Schneider Electric
Meter manufacturer
Vendor_Identifier
R
10
The BACnet vendor identifier for Schneider Electric
Model_Name
R
iEM3165, iEM3265, 
iEM3365
Device model (for example, iEM3265) and serial number in the format <model 
name>_<serial number> (for example, iEM3265_0000000000).
Firmware_Revision
R
varies
BACnet firmware version, stored in an x.x.x format (for example, 1.7.2).
Application_Software_Version
R
varies
Meter firmware version, stored in an x.x.xxx format (for example, 1.0.305).
Description
R/W
configurable
Optional description of the meter, limited to 64 characters.
Location
R/W
configurable
Optional description of the meter’s location, limited to 64 characters.
Protocol_Version
R
varies
BACnet protocol version (for example, version 1)
Protocol_Revision
R
varies
BACnet protocol revision (for example, revision 6)
Protocol_Services_Supported
R
0000 0100 0000 1011 
0100 0000 0000 0000 
0110 0000
The BACnet services supported by the meter: subscribeCOV, readProperty, 
readPropertyMultiple, writeProperty, deviceCommunicationControl, who-HAS, 
who-Is
Protocol_Object_Types_Supported R
1011 0000 1000 0000 
0000 0000 0000 0000
The BACnet object types supported by the meter: analog input, analog value, 
binary input, device
Object_list
R
varies
List of objects in the meter:
iEM3165 / iEM3365: DE1, AI0-AI48, AV0, BI0-BI6
iEM3265: DE1, AI0-AI55, AV0, BI0-BI6
Max_APDU_Length_Accepted
R
480
The maximum packet size (or application protocol data unit) that the meter can 
accept, in bytes
Segmentation_Supported
R
0x03
The meter does not support segmentation.
Local_Date
R
configurable
Date
NOTE: You must use the front panel to set the meter’s date.