Bosch FPA-1000 Manuale Utente

Pagina di 8
use these devices on addresses above 127 and other
devices below address 127. All compatible detectors
and modules are addressed using the D5070
Programmer.
Parts Included
Quant.
Component
1
FPA‑1000‑V2 main board
1
Enclosure with transformer
1
Enclosure lock and two keys
1
 (replacement key: D102)
1
Hardware pack
3
Wiring labels (one each in English, Spanish, and
Portuguese)
2
2.21 kΩ EOL resistors (replacement resistors: EOL‑2.2K, 8
per package)
 
Tabs with different language versions for LED and key text
 
Literature (in English, Spanish, and Portuguese)
• Installation and Operation Guide
• Operating Instruction Sheet
• Release Notes
1
 Key code stamped on both lock and key
Technical Specifications
Electrical
Power supply (primary)
• Current:
120 VAC: 2 A maximum
240 VAC: 1 A maximum
• Voltage:
120 VAC, 60 Hz or 240 VAC, 50 Hz
Power supply (secondary)
• Current (alarm):
• Panel < 0.240 A
• SLC = 0.63 A maximum
• Current (load):
Standby: < 1.25 A
 
Alarm: 4 A Shared maximum
• NAC 1 = 2.5 A maximum
• NAC 2 = 2.5 A maximum
• AUX/FWR = 0.5 A maximum
• AUX/RST = 0.5 A maximum
• Option bus = 0.5 A maximum
• Voltage:
24 VDC
Batteries
• Voltage:
2 x 12 VDC in series
• Capacities:
maximum 40 Ah
• in cabinet: 7 Ah to 18 Ah
• in additional battery box: 24 Ah
to 40 Ah
• Fuses:
15 A blade type
Auxiliary power supply (AUX)
• AUX/FWR:
0.5 A at 24 V FWR
Non‑switched, power‑limited, unfiltered,
unsupervised
• AUX/RST:
0.5 A at 24 VDC
Switched, power‑limited, filtered,
unsupervised
Environmental
Environment:
Indoor, dry
Protection Class:
IP 30
Relative Humidity:
Up to 95%, non-condensing
Temperature (operating):
+32°F to +120°F (0°C to +49°C)
Temperature (storage):
+14°F to +131°F (-10°C to +55°C)
Mechanical
Operating Elements
 
• LCD:
4‑line x 20‑character display, backlit
• LEDs:
Six total: Fire, Gas Alarm, Power,
Supervisory, Silenced, and Trouble
• Operation Keys:
Drill, Reset, Silence, and Acknowledge
• Alphanumeric
Keypad:
12 alphanumeric keys, escape, enter,
and navigation buttons (left, right, up,
down)
Interfaces
 
• PSTN/DACT:
2 lines, RJ45
• Ethernet:
1 x RJ45
• Peer-to-peer
communication:
Each interconnected panel requires one
of the following:
• FPE‑1000‑NE Networking Card
3‑Ethermet
• FPE‑1000‑NF Networking Card
1‑Ethernet 2‑Fiber Optic
• FPE‑1000‑NW Networking Card
1‑Ethernet 2‑Wired
Network Connections
 
• Ethernet:
minimum of CAT 5 cable at a maximum
length of 328 ft (100 m)
• Fiber Optics:
multi-mode fiber optic cable (62.5 μm/
125 μm fiber size; 1270 nm to 1380 nm
wavelength) with LC connectors at a
maximum length of 6560 ft (2000 m or a
10 db loss, whichever occurs first)
• Wired:
12 AWG (2.05 mm) to 26 AWG
(0.41 mm) twisted pair wire (shielded or
unshielded) at a maximum length of
2952 ft (900 m) or CAT 5 cable or better
at a maximum length of 3280 ft
(1000 m)
Wiring
 
• Cable Entries:
Triple knock-outs (3/4, 1/2, 1 in)
4 | FPA‑1000 Analog Addressable Fire Panels