ADT Security Services 9600 Manuale Utente

Pagina di 148
2SHUDWLQJ,QVWUXFWLRQV
6XSHUYLVRU\2SHUDWLRQ

8QLPRGH31&
• Second line in display:
✓ <ADJ>; refers to the user programmed adjective descriptor from library list 
resident in the control panel or custom entry via PC.
✓ <NOUN>; refers to the user programmed noun descriptor from library list 
resident in the control panel or custom entry via PC.  
• Third line in display: Z000 indicates the zone programmed to this device which, in 
this example, is general alarm Zone 000.  Note that a single device can be 
programmed to five different zones but only the first zone will be displayed.
• Fourth line in display:
✓ Time; the current time in this example is 10:00A which represents 10:00 AM
✓ Date; the current month, day and year in this example is 01 for January, 08 for the 
8th day of the month and 01 for the year 2001
✓ Device Address; 1M001 in this example 1 represents SLC Loop1, M represents a 
module and 001 represents device address 001
4.6  Supervisory Operation
Supervisory operation is similar to alarm operation but with the following differences:
• The piezo sounder pulses ½ second On and ½ second Off
• The Supervisory LED flashes ½ second On and ½ second Off
• The LCD displays the status label Active Supervisory along with the device name, 
type, address, adjective/noun, associated zones and time/date
• The supervisory relay is activated
• The alarm relay is not activated
• Silenced alarms are not resounded
• Timers are not started
• Store event in history buffer
A typical Supervisory event would be displayed as illustrated in the following:  
Note that, like alarms, supervisory signals latch (except when programmed for 
supervisory autoresettable) and can be assigned to software zones.  Supervisory alarms do 
not cause resound as do other alarm conditions.  Open circuits in supervisory wiring are 
processed by the control panel the same way as other trouble conditions.  Refer to  "Alarm 
Operation" on page 109, for a description of the information displayed on the control 
panel LCD.
ACTIVE  SUPERVISORY
    <ADJ> <NOUN>
                Z000
 10:00A 010801 1M001