3.2  User Programming
The Unimode 9600 is completely field programmable and requires no special software 
skills.  While programming the Unimode 9600, the fire protection capabilities of the 
control panel are enabled. 
Site-specific programming may be accomplished in three ways:
• Autoprogramming Feature - This is a convenient method for quickly bringing the 
FACP addressable SLC devices on-line without the necessity of programming each 
device individually.  Refer to  "Autoprogram" on page 87 for a detailed description 
of Autoprogramming
• Manual programming or editing, using the FACP keypad or a PC keyboard
• Off-line Programming and Editing Feature - allows creation and editing of site-
specific custom programs using a Windows-based computer.  For programs 
requiring a large amount of data entry, this method may be preferred.  A PK-9600 
programming kit can be ordered for this purpose
The System All Normal screen will be displayed in a programmed system with no active 
alarms, troubles or supervisories, as illustrated below: 
Programming and Read Status mode can be entered while the panel is in any mode of 
operation.  If the panel is in alarm, the alarm condition must be acknowledged before 
entering other modes.  To access any of the programming or read status features, the Enter 
or Mode key must be pressed, which will cause the LCD to display the following: 
Pressing 1, while this screen is being displayed, will cause the control panel to enter the 
Read Status feature which allows the user to view the programmed features and status of 
the control panel  The Read Status feature is not password protected.  Refer to  "Read 
Status" on page 117 for a detailed description of this feature.
Pressing 2 will select user Programming which may only be accomplished by an 
authorized person.  After pressing 2, a screen will prompt for a password.  After entering 
the correct password, the user may select from a list of programming options.
Exit Programming or Read Status  
The programmer can exit Read Status or Programming mode by repeatedly pressing the 
keypad ESC (Escape) key until the display reads System All Normal.  Note that the data 
which is entered during Programming mode is not saved until the programmer exits this 
mode by repeatedly pressing the ‘ESC’ key.  If the Reset key is pressed or power is lost 
before exiting Programming mode, all data which was just entered will be lost
.
!!!
 SYSTEM@ALL@NORMAL
 10:00A@010801
1=READ@STATUS
2=PROGRAMMING