ADT Security Services 9600 Manuale Utente

Pagina di 148
0DVWHU3URJUDPPLQJ/HYHO
3URJUDPPLQJ
8QLPRGH31&

3.6.5  Autoprogram
Pressing 2 while viewing Programming Screen #2, will select the Autoprogram option, 
which prompts the control panel to poll all devices installed on one or both SLC loops.  
The primary purpose of autoprogramming is to allow the installer a fast and easy way to 
bring the system on-line as quickly as possible.  The first time the system is powered-up, it 
should be autoprogrammed.
If the system is already programmed and Autoprogram is initiated, the system will only 
add default values for newly installed devices.
When Autoprogram is selected, the programmer is given the option of autoprogramming 
all loops, only loop 1 or only loop 2.  The following will be displayed on the LCD: 
After selecting one of the Autoprogram options, the control panel will begin 
autoprogramming the system by communicating with each addressable device installed on 
one or both loops.  While autoprogramming, the panel will display the following: 
When Autoprogramming is completed, the control panel will display the type and quantity 
of each device installed on the SLC loop(s) similar to the following display:
In the preceding example, the first display indicates that Loop 1 has 55 addressable 
detectors, 35 monitor modules and 30 control modules installed.  The second display 
indicates that Loop 2 has no devices installed.
    PROGRAMMING
1=SYSTEM SETUP
2=AUTOPROGRAM
3=VERIFY LOOPS
Programming Screen #2
@@@@AUTOPROGRAM
1=LOOP@1
2=LOOP@2
3=ALL@LOOPS
Autoprogram Loop Select Screen  
@@@@AUTOPROGRAM
@@AUTOPROGRAMMING!
@@@@PLEASE@WAIT
Autoprogram Progress Screen  
#@OF@DET@LOOP1@055
#@OF@MON@LOOP1@035
#@OF@CON@LOOP1@030
#@OF@DET@LOOP2@000
#@OF@MON@LOOP2@000
#@OF@CON@LOOP2@000
Autoprogram Result Screen #1  
Autoprogram Result Screen #2