LST GM-55000-137 Dépliant

Pagina di 1
© LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231 WIEN • WIEGELESTRASSE 36 • TEL +43 1 52114-0 • FAX +43 1 52114-27
OFFICE@LST.AT • WWW.LST.AT • ALL RIGHTS RESERVED
GM-55000-137_DBL_LST_EN_0804.PDF • PAGE 1
A
Building Safety. Building Security.
•  Addressable conventional technology
•  Alarm temperature 90°C
•   Individual detector addressing by 
means of optional address module
•   Optional connection of remote 
indicator
•   Sealed electronics
Description
Specifi cations
The Thermal Max Detector GM-55000-137 recognises 
a maximum temperature of 90°C as sign of fi re. It com-
plies with Class CS and can be used up to a room height 
of 6m.
Addressable conventional technology is used for alarm 
transmission  to  the  fi re  detection  control  panel.  By 
means of the optional Address Module NG60-1, each 
detector can be addressed individually. With that, the 
activated detector can also be safely identifi ed directly 
on the control panel.
The detector can be attached to various bases and it 
can be protected against theft.
Operating voltage 
Supply through the detector line voltage
Current consumption 
typ. 45µA (quiescent)
Alarm temperature 
typ. 90°C
Operating temperature 
max. +80°C (continuous operation)
Ambient temperature 
-20°C to +90°C (no condensation or icing)
Relative humidity 
0 – 95% (no condensation)
Dimensions ø × H 
100 × 42 (mm)
Colour 
white
Weight 
80g
Approval 
VdS G200062
Order number 
242027
Order name 
Thermal Max Detector/Conv./65/Apo GM-55000-137