Description
The Manual Call Points Series MCP5A are certifi ed to 
the standard EN 54-11/A and are designed for use in 
ADM loops with System Sensor/200 protocol.
Two mechanical versions of the detector are available:
  •  With  pane  of  glass:  The  detector  is  activated  by 
pressing  in  the  pane  of  glass,  which  breaks  into 
two pieces at a predetermined breaking point. By 
means of a special key, the detector case can be 
opened and the pane of glass can be replaced.
  •  With pane of plastic: The detector is activated by 
pressing in the pane of plastic without breaking it. 
By means of a special key, the pane can be put 
back to the idle position, thereby resetting the de-
tector.
Each of these two mechanical versions is available with 
or without dual-isolator. The integrated dual-isolator dis-
connects the adjacent loop elements fast and safely in 
case of a short circuit.
The activated condition of the manual call point is opti-
cally indicated by an LED. The detector address is se-
lected with two decadic rotary switches.
The  detector  is  fi tted  into  a  plastic  case  and  can  be 
mounted  on  a  60mm  fl ush-mount  installation  box.  An 
optional  case  for  surface  mounting  on  a  wall  can  be 
supplied.
•   ADM loop technology with
System Sensor/200 protocol
•   Available with pane of glass or plastic
•   LED indicates activation
•   Versions with or without dual-isolator
•   Operating instructions by means of 
standardised symbols
Operating voltage 
Supply through loop voltage
Ambient temperature 
-10°C to +55°C (no condensation or icing)
Relative humidity 
max. 95% (no condensation)
Protection class 
IP24
Dimensions W × H × D 
89 × 93 × 28 (mm)
Colour 
fl ame red, RAL 3000
Weight 
110g
Approval 
LPCB 166b/45, 166b/46
Manual call point with pane of glass, without isolator MCP5A-RP07FG
Current consumption 
260µA (quiescent)
Order number 
245040
Order name 