LST AD-58000-400 Dépliant

Pagina di 2
© LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231 WIEN • WIEGELESTRASSE 36 • TEL +43 1 52114-0 • FAX +43 1 52114-27
OFFICE@LST.AT • WWW.LST.AT • ALL RIGHTS RESERVED
AD-58000-400_DBL_LST_EN_0804.PDF • PAGE 1
A
Building Safety. Building Security.
•   ADM loop technology with 
Apollo/Discovery protocol
•   For use as maximum heat or 
rate-of-rise heat detector
•   5 different operating modes 
selectable
•   Optional connection of remote 
indicator
•   Sealed electronics
Description
The  addressable  Thermal  Detector  AD-58000-400  is 
based on the heat principle and was developed for the 
indoor temperature supervision in a wide range of fi re 
detection applications.
Depending on the parameter setup in the fi re detection 
control panel, the detector operates either as maximum 
heat detector with an alarm temperature of 61°C (EN 
54-5  Class  A2S)  or  90°C  (EN  54-5  Class  CS),  or  as 
rate-of-rise heat detector with a maximum temperature 
of 58°C (EN 54-5 Class A1R), 61°C (EN 54-5 Class A2) 
or 90°C (EN 54-5 Class CR). In Class A1R the detector 
can be used up to a room height of 7.5m, in the other 
operating modes a room height of 6m is permissible.
The proven ADM loop technology with Apollo/Discovery 
protocol establishes a permanent communication bet-
ween the fi re detection control panel and the detector. 
That ensures a periodical function testing of the detec-
tor.  Fires  are  safely  detected  in  the  control  panel  by 
continuously analysing the measured values.
The two LEDs with 360° visibility indicate the activated 
condition of the detector. The detector address is se-
lected by means of a code card in the detector base. 
Therefore the detector can be changed without additi-
onal tools.
The detector can be attached to various bases and it 
can be protected against theft.