American Standard 0291.008 Dépliant

Pagina di 1
J31
BARRIER FREE
© 2008 AS America Inc.
400mm
(15-3/4")
457mm
(18")
584mm
(23")
203mm
(8")
FINISHED FLOOR
*
254mm
(10")
*
295mm
(11-5/8")
19mm
(3/4")
197mm
(7-3/4")
OPTIONAL
224mm
(8-7/8")
SUPPLIES
AS REQ'D
203mm
(8")
FINISHED WALL
OR SPLASHBACK
1-1/4 O.D.
WASTE
1-3/4" DIA.
STD. DRAIN
OUTLET
1-1/4" O.D.
TAILPIECE
SEALING COMPOUND
(BY OTHERS)
COUNTERTOP
(BY OTHERS)
3 Holes
1-3/8" (35mm) Dia.
178mm
(7")
787mm (31)
845mm (33-1/4)
845mm
(33-1/4)
51mm
(2)
610mm
(24)
152mm
(6)
MAX.
BARRIER FREE
CLEARANCE
686mm
(27)
MIN.
203mm
(8)
MIN.
229mm
(9)
MIN.
DRAWING FOR 
DIMENSIONAL 
PURPOSES ONLY. 
IT IS NOT AN EXACT 
REPRESENTATION.
RETROSPECT COLLECTION
®
COUNTERTOP SINK
FINE FIRECLAY
RETROSPECT COLLECTION
®
 
COUNTERTOP SINK
•  Classically-styled countertop sink
•  Retrofits in any 20" x 17" cutout
•  Made from fireclay china
•  Front overflow
•  Self-rimming with cutout template supplied
• 
Part of design matched Retrospect Collection
®
 
0291.004 Faucet holes on 4" (203mm) centers
 
0291.008 Faucet holes on 8" (102mm) centers
 
(illustrated)
Nominal Dimensions:
584 x 457mm 
(23" x 18")
 
Bowl sizes: 
422mm (16-5/8") wide
286mm (11-1/4") front to back
159mm (6-1/2") deep
Compliance Specifications -
Meets or Exceeds the 
Following Specifications:
• ASME A112.19.9M for 
  Non-Vitreous Ceramic Fixtures
• CAN/CSA B45 Series
MEETS THE AMERICAN DISABILITIES ACT GUIDELINES AND 
ANSI A117.1  ACCESSIBLE AND USABLE BUILDINGS AND 
FACILITIES - CHECK LOCAL CODES.
Install lavatory 864mm (34") from finished floor.
Lavatory installed 51mm (2") minimum from front edge of countertop 
provides 686mm (27") knee clearance area.
To Be Specified:
  Color: White only
  Recommended Faucet: 2373.701 
  Faucet Finish: 
  Supplies:
  1-1/4" Trap
NOTES:
*
 DIMENSIONS SHOWN FOR LOCATION OF SUPPLIES AND “P" TRAP 
ARE SUGGESTED.
FOR COUNTERTOP CUTOUT AND INSTALLATION INSTRUCTIONS USE 
TEMPLATE SUPPLIED WITH SINK.
FITTINGS NOT INCLUDED WITH FIXTURE AND MUST BE ORDERED 
SEPARATELY.
SEALING COMPOUND SUPPLIED BY OTHERS.
IMPORTANT:  Dimensions of fixtures are nominal and may vary within the 
range of tolerances established by ANSI Standard A112.19.9M.
These measurements are subject to change or cancellation. No responsibility 
is assumed for use of superseded or voided pages.
Revised 5/06