5. Main Circuit Connections and 
Disconnecting/Removing the Circuit 
Breaker from the Cell 
5.1 Connecting the Main Circuit (disconnected position to connected 
position) 
 
Perform the steps shown in Figures 20 through 21 in that order. 
 
 
To avoid damaging the equipment, do not connect or disconnect the 
main circuit when the unit switching status is ON. 
To prevent electric shock or other injury, do not bend or modify the 
in/out interlock attached the unit.
 
 
 
 
To avoid injury and damage to the equipment, do not remove the 
holding pin unless you are moving the VCB outside the panel. 
To prevent electric shock or other injury, follow the instructions given in 
the instruction manual when moving the equipment in or out of the 
panel.
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Figure 20 Insert the control circuit 
connector into the port on the VCB.
Figure 21 Grasp the handle with both hands 
and, with the interlock lever in the raised 
position, insert the VCB up to the 
connected position. 
* The interlock lever cannot be raised when 
the switching status of the VCB is set to 
ON. Perform the open circuit operation   
and set the switching status to OFF. 
       
CAUTION 
       
WARNING