Emerson Model 1700 Manuale Utente

Pagina di 350
Procedure
1.
Select the event that you want to configure.
2.
Specify Event Type.
Options
Description
HI
x > A
The event occurs when the value of the assigned process variable (x) is
greater than the setpoint (Setpoint A), endpoint not included.
LO
x < A
The event occurs when the value of the assigned process variable (x) is
less than the setpoint (Setpoint A), endpoint not included.
3.
Assign a process variable to the event.
4.
Set a value for Setpoint A.
5.
(Optional) Configure a discrete output to switch states in response to the event
status.
6.5.2
Configure an enhanced event
Display (standard)
Not available
Chinese-language
display
Not available
ProLink II
ProLink
 > Configuration > Discrete Events
ProLink III
Device Tools
 > Configuration > Events > Enhanced Events
Field Communicator Configure > Alert Setup > Discrete Events
Overview
An enhanced event is used to provide notification of process changes and, optionally, to
perform specific transmitter actions if the event occurs. An enhanced event occurs (is ON)
if the real-time value of a user-specified process variable moves above (HI) or below (LO) a
user-defined setpoint, or in range (IN) or out of range (OUT) with respect to two user-
defined setpoints. You can define up to five enhanced events. For each enhanced event,
you can assign one or more actions that the transmitter will perform if the enhanced event
occurs.
Procedure
1.
Select the event that you want to configure.
2.
Specify Event Type.
Integrate the meter with the control system
100
 Micro Motion
®
 Model 1700 Transmitters with Analog Outputs