Emerson Model 1700 Manuale Utente
6
Integrate the meter with the control
system
Topics covered in this chapter:
•
•
•
•
•
•
6.1
Configure the transmitter channels
Display (standard)
OFF-LINE MAINT
> OFF-LINE CONFG > IO > CH B
Chinese-language
display
display
Offline Maintain
> Configuration > Input/Output > Channel B Setup
ProLink II
ProLink
> Configuration > Frequency/Discrete Output
ProLink III
Device Tools
> Configuration > I/O > Channels
Field Communicator Configure > Manual Setup > Inputs/Outputs > Channels > Channel B
Overview
You can configure Channel B on your transmitter to operate as a frequency output or a
discrete output. The channel configuration must match the wiring at the transmitter
terminals.
discrete output. The channel configuration must match the wiring at the transmitter
terminals.
Prerequisites
To avoid causing process errors:
•
Configure the channels before configuring the outputs.
•
Before changing the channel configuration, ensure that all control loops affected by
the channel are under manual control.
the channel are under manual control.
Procedure
Set Channel B as desired.
Option
Description
Frequency output
Channel B will operate as a frequency output.
Discrete output
Channel B will operate as a discrete output.
Integrate the meter with the control system
80
Micro Motion
®
Model 1700 Transmitters with Analog Outputs