Lochinvar SNA285-125 Manuale Utente

Pagina di 76
20
2  
General
 
venting
       
Installation & Service Manual
TM
Installing vent and air piping
Use only cleaners, primers, and solvents 
that are approved for the materials which 
are joined together.
 NOTICE
1.  Work from the water heater to vent or air termination.  
 
Do not exceed the lengths given in this manual for the 
 
air or vent piping.
2.  Cut pipe to the required lengths and deburr the inside 
 
and outside of the pipe ends.
3.  Chamfer outside of each pipe end to ensure even 
 
cement distribution when joining.  
4.  Clean all pipe ends and fittings using a clean dry rag.  
 
(Moisture will retard curing and dirt or grease will prevent 
 adhesion.)
5.  Dry fit vent or air piping to ensure proper fit up before 
 
assembling any joint.  The pipe should go a third to         
 
two-thirds into the fitting to ensure proper sealing after 
 
cement is applied.
6. Priming 
and 
Cementing:
 
a.  Handle fittings and pipes carefully to prevent 
  contamination 
of 
surfaces.
 
 
b.  Apply a liberal even coat of primer to the fitting 
 
 
socket and to the pipe end to approximately 1/2" 
 
 
beyond the socket depth.
 
 
c.  Apply a second primer coat to the fitting socket.
 
 
d.  While primer is still wet, apply an even coat of 
 
 
approved cement to the pipe equal to the depth of 
 
 
the fitting socket along with an even coat of 
 
 
approved cement to the fitting socket.
 
 
e.  Apply a second coat of cement to the pipe.
 
 
f. 
While the cement is still wet, insert the pipe into 
 
 
the fitting, if possible twist the pipe a 1/4 turn as 
 
 
you insert it.  NOTE:  If voids are present, 
 
 
sufficient cement was not applied and joint could 
  be 
defective.
 
 
g. 
Wipe excess cement from the joint removing ring or 
 
 
beads as it will needlessly soften the pipe.
PVC/CPVC
Table 2D PVC/CPVC Vent Pipe, and Fittings
All PVC vent pipes must be glued, properly 
supported, and the exhaust must be pitched 
a minimum of a 1/4 inch per foot back to 
the water heater (to allow drainage of 
condensate).
 NOTICE
 WARNING The vent connection to the appliance must 
be made with the starter CPVC pipe section 
provided with the appliance if PVC/CPVC 
vent is to be used.  The field provided 
vent fittings must be cemented to the 
CPVC pipe section using an “All Purpose 
Cement” suitable for PVC and CPVC pipe.  
Use only the vent materials, primer, and 
cement specified in Table 3D to make 
the vent connections.  Failure to follow 
this warning could result in fire, personal 
injury, or death.
 WARNING
Insulation should not be used on PVC 
or CPVC venting materials.  The use of 
insulation will cause increased vent wall 
temperatures, which could result in vent 
pipe failure.
Approved PVC/CPVC Vent Pipe and Fittings
Item
Material
Standard
Vent pipe
PVC Schedule 40, 80 ANSI/ASTM D1785
PVC - DWV
ANSI/ASTM D2665
CPVC Schedule 40, 80 ANSI/ASTM F441
Vent fittings
PVC Schedule 40
ANSI/ASTM D2466
PVC Schedule 80
ANSI/ASTM D2467
CPVC Schedule 80
ANSI/ASTM F439
Pipe Cement / 
Primer
PVC
ANSI/ASTM D2564
CPVC
ANSI/ASTM F493
NOTICE:  DO NOT USE CELLULAR (FOAM) CORE PIPE
Figure 2-7 Near Water Heater PVC/CPVC Venting 
This product has been approved for use with the PVC/CPVC 
vent materials listed in Table 3D.
NOTE:  In Canada, CPVC and PVC vent pipe, fi ttings and cement/
primer must be ULC-S636 certifi ed.
VENT
4" CPVC PIPE INSTALLED IN THE
WATER HEATER MUST BE USED
FOR VENT CONNECTION
NOTE:  CPVC VENT PIPE AND VENT FITTINGS MUST BE USED 
IN CLOSET AND ALCOVE INSTALLATIONS.