Lochinvar SNA285-125 Manuale Utente

Pagina di 76
 
 
39
6  
Gas connections
Connecting gas supply piping
1.  Install ground joint union for servicing, when 
 required. 
 
2.  On Models SNR150-100 -- SNA285-125 install a manual 
 
shutoff valve in the gas supply piping outside water heater 
 
jacket when required by local codes or utility requirements.
 
3.  In Canada – When using manual main shutoff valves, it 
must be identified by the installer.
GAS SUPPLY
DRIP LEG
MANUAL GAS
SHUT OFF VALVE
(FIELD SUPPLIED)
UNION
Figure 6-1 Gas Supply Piping - Models SNR150-100 
-- SNA285-125
4.  Support piping with hangers, not by the water heater or its 
accessories.
Do not check for gas leaks with an open 
flame – use the bubble test. Failure to use the 
bubble test or check for gas leaks can cause 
severe personal injury, death, or substantial 
property damage.
GAS SUPPLY
DRIP LEG
MANUAL GAS
SHUTOFF VALVE
(FACTORY SUPPLIED ON
MODELS SNA400-125 --
SNA500-125)
UNION
Figure 6-2 Gas Supply Piping - Models SNA400-125 
-- SNA500-125
5.  Purge all air from the gas supply piping.
6.  Before placing the water heater in operation, check the 
water heater and its gas connection for leaks.
 
 
a.  The appliance must be disconnected from the gas 
  
supply piping system during any pressure testing of 
  
that system at a test pressure in excess of 1/2 PSIG 
  
(3.5  kPa).
 
b.  The appliance must be isolated from the gas supply 
 
 
piping system by closing a manual shutoff valve 
 
 
during any pressure testing of the gas supply piping 
 
 
system at test pressures equal to or less than 1/2 PSIG 
  (3.5 
kPa).
 
c.  The appliance and its gas connection must be leak 
 
 
tested before placing it in operation.
The gas valve and blower will not support 
the weight of the piping. Do not attempt to 
support the weight of the piping with the 
water heater or its accessories. Failure to 
comply could result in severe personal injury, 
death, or substantial property damage.
 WARNING
 WARNING
7.  Use pipe sealing compound compatible with propane gases.  
Apply sparingly only to male threads of the pipe joints so 
that pipe dope does not block gas flow.
       
Installation & Service Manual