Operating information 
(continued)
 
OPERATION
DISPLAY
1.  When the tank temperature falls below the set point minus the 
differential, the control will start the burner.
HTR: Standby
TANK: 123.8F(129)
2.  The control connects 120 VAC to the blower.  The blower does 
not run at this time.
 
•  The manual reset high limit must be closed before the control 
   powers up the blower.
 
•  The control starts the internal pump.
 
•  If there is an external limit connected to the heater, it must be 
   closed.
HTR: Standby
TANK: 123.8F(129)
3.  The control then starts the prepurge cycle.  
HTR: PREPURGE
TANK: 123.9F(129)
4.  Once the prepurge cycle is complete, and the blocked drain  
 
switch and auto-reset high limit are closed, the control starts the                 
 
trial for ignition by sending spark voltage to the spark electrode 
      and opening the gas valve.
HTR: IGNITION
TANK: 123.9F(129)
5.  If the control does not detect flame by the end of the trial for 
 
ignition, the control performs the postpurge, another prepurge 
     and tries to light the burner again.  If the burner does not light 
       after 4 trials, the control locks out for 1 hour and then tries another 
      set of 4 trials.
HTR: POSTPURGE, PREPURGE
TANK: 123.9F(129)
6.  If the control detects a flame before the trial for ignition ends, it 
 
begins to modulate the burner in order to maintain the set point.   
 
HTR: RUN 20% RATE
TANK: 124.8F(129)
7.  Once the tank temperature goes 3 - 4°F above the set point, the 
control will turn off the burner.  The blower will remain on for the 
postpurge cycle.  The internal pump will continue to run for its 
pump delay time, then turn off.
HTR: POSTPURGE
TANK: 127.4F(129)
8. Burner off.
HTR: Standby
TANK: 124.7F(129)
Sequence of operation
       