Troubleshooting 
Table 12E Troubleshooting Chart - Fault Messages Displayed on Water Heater Interface 
FAULT
DESCRIPTION
CORRECTIVE ACTION
Flame 
Sequence
(will require a manual 
reset once the condition 
has been corrected.  
Press the RESET button 
on the display to reset.)
The flame detector circuit is seeing a flame 
signal while no flame is present.
 • Check supply voltage for proper polarity.
 • Check external wiring for voltage feedback.
 • Check the flame rod and make sure it is clean.
 • Check the internal wiring for bad connections.
 • Replace main control board.
No Flame Ign
(will require a manual 
reset once the condition 
has been corrected.  
Press the RESET button 
on the display to reset.)
The unit has failed to prove main burner 
ignition after four (4) attempts.
•  Ensure gas valve switch is ON (Models SNR150-100 
 and 
SNA285-125).
•  Check wiring harness connection at the gas valve and 
  at the main control board.
• Inspect spark electrode and associated wiring for 
  damage and connection.  Reference page 60 of this 
 manual for removal and cleaning procedures. 
 
  Replace if necessary.
•  Check for proper electrical grounding of the unit.
• Check incoming supply gas pressure.  Natural gas 
  pressures should be between 4 - 14 inches w.c. and 
 LP gas pressures should be between 8 - 14 
 
 
 
 
   
  inches w.c. Refer to Section 6 - Gas Connections for 
  detailed information concerning the gas supply.
• Verify that the plastic hose from the gas valve to the 
  air inlet is connected and is not damaged.
• Verify that the vent/air intake pipes are correctly 
  installed and that there are no obstructions.
• Check for 24 VAC to the gas valve at the 2-pin 
  connection on the side of the main control board 
  during the ignition attempt.  If no voltage is present, 
  replace the main control board.
•  If 24 VAC is present at the main control board, check 
  the wiring between the main control board and the 
  gas valve.  Replace the wiring if necessary.  
• If 24 VAC is present, check the outlet of the valve to 
  ensure the valve is flowing gas. With a manometer 
  connected to the outlet tap of the gas valve, when the 
  unit is in the prepurge period, there should be a 
 negative pressure present. When the valve is 
  energized a change in pressure should occur.  If the 
  pressure change does not occur, the gas valve is not 
  opening.  Replace the gas valve.
• 
Inspect flame sensor and associated wiring. 
 
  Reference page 60 of this manual for removal and 
  cleaning procedures.  Replace if necessary.
•  Inspect the burner.  Reference page 60 of this manual 
  for removal and cleaning procedures. Replace if 
 necessary.
•  Replace the main control board.
       