T7200D,E, T7300D,E,F AND Q7300 SERIES 2000 PROGRAMMABLE COMMERCIAL THERMOSTATS AND SUBBASES
15
63-4355—4
Table 9. Installer System Test Options.
Key to Press
Test 
Number
Description
Heating Equipment System Test
Heat/Cool Settings
10
Enter heating equipment system test.
▲ 
11
Stage-one heat turns on. The system fan is also energized.
▲ 
12
Stage-two heat turns on. Stage-one heat and system fan remain on.
▲ 
13
Stage-three heat turns on. Stage-one and stage-two heat with the system fan are on.
▼ 
12
Stage-three heat turns off.
▼ 
11
Stage-two heat turns off.
▼ 
10
Stage-one heat and system fan turn off.
Emergency Heating Equipment System Test (T7300E,F with Q7300C,D)
Heat/Cool Settings
20
Change from heating to emergency heating equipment system test (Em Heat on).
▲ 
21
Fan turns on.
20
Fan and highest stage heat turns off.
Cooling Equipment System Test
Heat/Cool Settings
30
Change from heating or emergency heating to cooling equipment system test.
▲ 
31
Stage-one cooling and system fan turn on.
▲ 
32
Stage-two cool turn on. Stage-one cool and system fan remain on.
▲ 
33
Stage-three cool turns on (Q7300G,H only). Stage-one and stage-two cool with system 
fan remain on.
▼ 
32
Stage-three cool turns off.
▼ 
31
Stage-two cool turns off.
▼ 
30
Stage-one cool and system fan turn off.
Fan Equipment System Test
Heat/Cool Settings
40
Change from cooling to fan equipment system test.
▲ 
41
Fan turns on.
▲ 
42
High speed fan turns on (Q7300Ha, L only).
▼ 
41
High speed fan turns off.
▼ 
40
Fan turns off.
Key Operation System Test
Heat/Cool Settings
60   2
Change from fan to key operation system test.
Unoccupied Temp
60   0
Unoccupied Temp test number is displayed.
Occupied Temp
60   1
Occupied Temp test number is displayed.
▲ 
60   3
Increase test number is displayed.
▼ 
60   5
Decrease test number is displayed.
Clear Start Time
60   7
Clear Start Time test number is displayed.
Day
60   8
Day test number is displayed.
Copy
60   9
Copy test number is displayed.
Unoccupied Start TIme
60   10
Unoccupied Start Time test number is displayed.
System (select models)
60   11
System test number is displayed.
Fan (select models)
60   12
Fan test number is displayed.
Set Current Day/Time
60   14
Set Current Day/Time test number is displayed.
Run Program
60   15
Run Program test number is displayed.
Temporary Occupied
60   16
Temporary Occupied test number is displayed.
Occupied Start Time
60   17
Occupied Start Time test number is displayed.
Continuous Unoccupied
60   19
Continuous Unoccupied test number is displayed.